10.Install the Sun Netra CP3250 blade server into the front of the ATCA shelf in the corresponding slot.
See Section 2.2.3.2, “Installing the Blade Server Into the Shelf” on page
2.2.3.2Installing the Blade Server Into the Shelf
Note – You can install the Sun Netra CP3250 blade server in any available slot in the ATCA shelf except for slots 7 and 8.
1.If you have installed an advanced rear transition module (ARTM), go to the front of the system and locate the corresponding slot number of the ARTM.
2.Remove the filler panel from the blade server slot, if necessary.
The filler panel is secured to the card cage using two screws, one at the top of the filler panel, the other at the bottom. Store the filler panel in a safe place; you might need to use it again if you remove a blade server for an extended time.
3.Prepare the Sun Netra CP3250 blade server by opening the injector/ejector latches.
4.Carefully align the edges of the blade server with the guides in the appropriate slot.
Look into the enclosure to verify correct alignment of the rails in the guides.
5.Keep the blade server aligned in the guides and slide the blade server in until the injector/ejector latches engage the card cage.
6.Push the blade server slightly into the backplane connectors and close the latches to seat the blade server in the connectors (FIGURE
Push the upper latch lever to engage the blade server. When the upper and lower levers are engaged properly, the blue
Note – If the