Check method

On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.

In case of check from indoor remote controller: See “Main remote controller display” in the list.

In case of check from outdoor unit: See “Outdoor 7-segment display” in the list.

In case of check from AI-NET central control remote controller: See “AI-NET central control display” in the list.

In case of check from indoor unit with wireless remote controller: See “Sensor block display of receiving unit” in the list.

Terminology

AI-NET : Artificial Intelligence.

IPDU : Intelligent Power Drive Unit

¡: Lighting, ¤: Flashing, l : Goes off

ALT. : Flashing is alternately when there are two flashing LED.

SIM : Simultaneous flashing when there are two flashing LED.

 

 

 

Check code

 

Wireless remote controller

 

 

 

 

 

 

 

 

 

 

 

Main

 

Outdoor 7-segment display

AI-NET central

Sensor block display

Check code name

Judging device

remote

 

 

 

of receiving unit

 

 

controller

 

 

 

control display

 

 

 

 

 

 

display

 

 

Auxiliary code

 

Operation

Timer Ready

Flash

 

 

 

 

 

 

 

 

 

 

 

 

 

E01

 

¤

 

 

 

Communication error between indoor and

Remote controller

 

 

 

 

 

 

 

 

 

l

l

 

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

(Detected at remote controller side)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E02

 

¤

l

l

 

Remote controller transmission error

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E03

 

97

¤

l

l

 

Communication error between indoor and

Indoor

 

 

 

 

 

 

remote controller (Detected at indoor side)

 

 

E04

 

04

l

l

¤

 

Communication circuit error between indoor/

Indoor

 

 

 

 

outdoor (Detected at indoor side)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of indoor units in which

 

l

l

¤

 

 

 

 

 

 

 

 

 

 

E06

E06

 

sensor has been normally

04

 

Decrease of No. of indoor units

I/F

 

 

 

 

 

received

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E07

 

l

l

¤

 

Communication circuit error between indoor/

I/F

 

 

 

 

outdoor (Detected at outdoor side)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E08

E08

 

Duplicated indoor addresses

96

¤

l

l

 

Duplicated indoor addresses

Indoor / I/F

 

 

 

 

 

 

E09

 

99

¤

l

l

 

Duplicated main remote controllers

Remote controller

 

 

 

 

E10

 

CF

¤

l

l

 

Communication error between indoor MCU

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01: Indoor/Outdoor

 

¤

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E12

E12

 

communication

42

l

l

 

Automatic address start error

I/F

 

 

 

02: Communication between

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E15

E15

 

42

l

l

¤

 

Indoor is nothing during automatic addressing

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

E16

E16

 

00: Capacity over

89

l

l

¤

 

Capacity over / No. of connected indoor units

I/F

 

 

 

 

 

01 ~:No. of connected units

 

 

 

 

 

 

 

 

 

 

 

 

E18

 

97, 99

¤

l

l

 

Communication error between indoor units

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E19

E19

 

00: Header is nothing

96

l

l

¤

 

Outdoor header units quantity error

I/F

 

 

 

02: Two or more header units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01: Outdoor of other line

 

 

 

¤

 

Other line connected during automatic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E20

E20

 

connected

42

l

l

 

I/F

 

 

 

02: Indoor of other line

 

address

 

 

 

 

 

connected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E23

E23

 

15

l

l

¤

 

Sending error in communication between

I/F

 

 

 

 

outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

E25

E25

 

15

l

l

¤

 

Duplicated follower outdoor addresses

I/F

 

 

 

 

E26

E26

 

No. of outdoor units which

15

l

l

¤

 

Decrease of No. of connected outdoor units

I/F

 

 

 

received signal normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E28

E28

 

Detected outdoor unit number

d2

l

l

¤

 

Follower outdoor unit error

I/F

 

 

 

 

 

 

 

 

01: IPDU1 error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02: IPDU2 error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03: IPDU1, 2 error

 

l

l

¤

 

 

 

 

 

 

 

 

 

 

E31

E31

 

04: Fan IPDU error

CF

 

IPDU communication error

I/F

 

 

 

 

 

05: IPDU + Fan IPDU error

 

 

 

 

 

 

 

 

 

 

06: IPDU2 + Fan IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07: All IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

Page 25
Image 25
Toshiba MMU-AP0071YH installation manual Check method, Check code list, Terminology

MMU-AP0071YH specifications

The Toshiba MMU-AP0071YH is an advanced motion control solution tailored for precise applications in various sectors, including industrial automation and robotics. This model exemplifies Toshiba's commitment to innovation and reliability, integrating cutting-edge technologies to streamline processes and enhance system performance.

One of the standout features of the MMU-AP0071YH is its superior motion control capabilities. It offers advanced servo control technology, ensuring highly accurate positioning and smooth motion transitions. This precision is critical for applications where even minor deviations can impact the overall system performance, such as in CNC machinery and robotic arms.

The MMU-AP0071YH is designed with flexibility in mind. It supports a wide range of interfaces, including EtherCAT, CANopen, and RS-232, allowing seamless integration with various systems and devices. This versatility facilitates easy implementation in existing setups, enabling manufacturers to upgrade their equipment without extensive modifications.

Another significant characteristic of the MMU-AP0071YH is its robust safety features. Safety is paramount in industrial environments, and Toshiba has incorporated multiple safety functions, such as Safe Torque Off (STO) and Safe Stop 1 (SS1). These features ensure the system can detect faults and respond appropriately to prevent accidents and protect both the machinery and operators.

Furthermore, the device is built to withstand demanding operational conditions. The MMU-AP0071YH is characterized by a compact and sturdy design, which is essential for environments that require high durability. The quality of the materials used in its construction also plays a vital role in its ability to operate effectively under various conditions.

In addition to its technical capabilities, the MMU-AP0071YH features user-friendly software tools that allow operators to configure, monitor, and manage motion tasks effortlessly. The user interface is intuitive, enabling engineers and technicians to access critical parameters quickly, thus optimizing performance and reducing downtime.

Overall, the Toshiba MMU-AP0071YH combines precision, versatility, and safety, making it a compelling choice for industries seeking reliable motion control solutions. Its innovative technology and robust design not only enhance operational efficiency but also contribute to the long-term sustainability of various manufacturing processes.