WARNING

 

After repair work, surely assemble the disassembled parts, and connect and lead the

 

removed cables as before. Perform the work so that the cabinet or panel does not

 

catch the inner cables.

Assembly/Cabling

If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or

fire is caused at user’s side.

 

 

 

 

After the work has finished, be sure to use an insulation tester set (500V mugger) to

 

check the resistance is 2MW or more between the charge section and the non-charge

 

metal section (Earth position).

Insulator check

If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s

side.

 

When the refrigerant gas leaks during work, execute ventilation.

 

If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the

 

refrigerant and the closed room full with gas is dangerous because a shortage of oxygen

Ventilation

occurs. Be sure to execute ventilation.

When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.

If touching to the charging section, an electric shock may be caused.

Be attentive to electric shock

When the refrigerant gas leaks, find up the leaked position and repair it surely.

If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room.

The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.

 

When installing equipment which includes a large amount of charged refrigerant such

 

as a multi air conditioner in a sub-room, it is necessary that the density does not the

Compulsion

limit even if the refrigerant leaks.

If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.

 

For the installation/moving/reinstallation work, follow to the Installation Manual.

 

If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric

 

shock or fire is caused.

 

 

 

After repair work has finished, check there is no trouble.

 

If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off

 

the power breaker.

 

 

Check after rerair

After repair work (installation of front panel and cabinet) has finished, execute a test

run to check there is no generation of smoke or abnormal sound.

 

 

If check is not executed, a fire or an electric shock is caused. Before test run, install the

 

front panel and cabinet.

 

 

 

Check the following items after reinstallation.

 

1) The earth wire is correctly connected.

 

2) The power cord is not caught in the product.

Check after reinstallation

3) There is no inclination or unsteadiness and the installation is stable.

 

If check is not executed, a fire, an electric shock or an injury is caused.

CAUTION

Be sure to put on gloves () during repair work.

If not putting on gloves, an injury may be caused with the parts, etc. () Heavy gloves such as work gloves

Put on gloves

When the power was turned on, start to work after the equipment has been sufficiently cooled.

Cooling check

As temperature of the compressor pipes and others became high due to cooling/heating

operation, a burn may be caused.

4

Page 4
Image 4
Toshiba MMU-AP0121MH Catch the inner cables, Fire is caused at user’s side, Metal section Earth position, Side

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.