77

Check code name

Check code name

Cause of operation

[H16]

Oil level detective circuit system error

1. Detachment of TK2 sensor, miscabling,

 

 

 

(Auxiliary code : 02)

characteristics error of resistance value

 

 

 

 

 

 

2. Oil-equalization circuit error

 

 

 

 

 

 

(Check valve, capillary clogging,

 

 

 

 

 

 

strainer clogging)

 

 

 

 

 

 

3. Refrigerant stagnation in compressor

 

 

 

 

 

 

shell

 

 

 

 

 

 

 

 

 

Is not TK2 sensor detached?

YES

 

 

Correct installation of sensor.

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct miscabling/misinstallation.

 

 

 

 

 

 

Is there no miscabling or misinstallation

YES

 

 

TK1: CN514

 

 

 

 

 

TK2: CN515

on TK1/TK2/TK3/TK4 sensors?

 

 

 

 

 

( TK3: CN516 )

 

 

 

 

 

 

 

 

 

NO

 

NO

 

 

TK4: CN523

 

 

 

 

 

 

 

 

 

 

Are characteristics of TK2 sensor

 

 

 

 

 

Sensor error

resistance value normal?

 

Outdoor unit temp sensor characteristics-4

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

Does OCR of MG-SW operate?

 

 

Reset OCR manually.( 2)

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After power reset

 

 

 

 

Error

 

 

 

 

 

 

 

Start a test operation in COOL or HEAT mode.

 

 

 

 

Replace clogging part.

 

 

 

 

 

 

 

 

 

 

 

 

TK2 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [12] [2].

Check TK2 sensor temp approx. 10 minutes after compressor 2 has operated.

If low temperature continues (approximately outside temp) or temperature

does not almost change, a clogging of strainer of oil-equalization circuit,

 

 

Compressor 2

clogging of capillary, or malfunction of check valve is considered.

 

 

 

 

 

 

 

 

 

 

 

 

 

No error

 

 

 

 

 

 

 

 

 

 

 

Strainer

 

 

 

 

 

Capillary tube

 

 

 

 

 

 

TK2

Check the clogging of SV3E valve.

Error

 

Oil tank

(*1)

1 Refer to item [H07] error.

 

 

 

 

 

 

 

No error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check I/F P.C. board

 

 

Replace SV3E valve.

 

 

 

 

 

 

 

 

2 If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (T02) of Comp-IPDU is correct or not.

Check code name

Check code name

Cause of operation

[H16]

 

TK3 temperature detective circuit error

1. Detachment of TK3 sensor, miscabling,

 

 

 

(Auxiliary code : 03)

characteristics error of resistance value

 

 

 

 

 

 

2. Error of SV3C valve circuit periphery

 

 

 

 

 

 

(Check capillary clogging, strainer

 

 

 

 

 

 

clogging)

 

 

 

 

 

 

3. Refrigerant stagnation in compressor

 

 

 

 

 

 

shell

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

Is not TK3 sensor come off?

 

 

Correct installation of sensor.

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct miscabling/misinstallation.

 

 

 

 

 

 

Is there no miscabling or misinstallation

YES

 

 

TK1: CN514

 

 

 

 

 

TK2: CN515

on TK1/TK2/TK3/TK4 sensors?

 

 

 

 

 

( TK3: CN516 )

 

 

 

 

 

 

 

 

 

 

NO

NO

 

 

TK4: CN523

 

 

 

 

 

 

Are characteristics of TK3 sensor

 

 

 

 

 

Sensor error Replace

 

 

 

 

 

resistance value normal?

* Outdoor unit temp sensor characteristics-4

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

After power reset,

 

 

 

 

 

 

 

 

check capillary choke of SV3C valve bypass.

 

 

 

 

 

 

 

 

Error

 

Start a test operation in COOL or HEAT mode.

 

Replace clogged part (Capillary).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TK3 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [13] [2].

Check TK3 sensor temp approx. 10 minutes after compressor 2 has operated.

Strainer

 

If low temperature continues (approximately outside temp) or temperature

 

does not almost change, a clogging of parallel capillary is considered.

 

 

 

 

 

No error

 

 

 

 

 

SV3E valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TK3

 

 

 

Error

 

 

 

 

Check the clogging of SV3E valve.

 

 

 

 

 

 

 

Replace SV3E valve.

 

 

 

 

 

(Note 1)

(Note 1) Refer to item [H07] error.

 

 

 

 

 

 

 

 

No error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check I/F P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 77
Image 77
Toshiba MMU-AP0091MH, MMU-AP0181MH Oil level detective circuit system error, TK3 temperature detective circuit error

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.