Toshiba MMU-AP0091MH Ventilating fan control from remote controller, Function, Operation, Wiring

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 42
Image 42

nVentilating fan control from remote controller

[Function]

The start/stop operation can be operated from the wired remote controller when air to air heat exchanger or ventilating fan is installed in the system.

The fan can be operated even if the indoor unit is not operating.

Use a fan which can receive the no-voltage A contact as an outside input signal.

In a group control, the units are collectively operated and they can not be individually operated.

(1)Operation

Handle a wired remote controller in the following procedure.

Use the wired remote controller during stop of the system.

Be sure to set up the wired remote controller to the header unit. (Same in group control)

In a group control, if the wired remote controller is set up to the header unit, both header and follower units are simultaneously operable.

1

Push concurrently SET + CL + TEST buttons for 4 seconds or more.

 

The unit No. displayed firstly indicates the header indoor unit address in the group control.

 

In this time, the fan of the selected indoor unit turns on.

2

Every pushing

UNIT

button, the indoor unit numbers in group control are displayed succes-

 

sively.

In this time, the fan of the selected indoor unit only turns on.

3

4

Using the setup temp

 

or

button, specify the item code !￿.

Using the timer time

or

 

button, select the setup data. (At shipment: ￿￿￿￿￿)

The setup data are as follows:

Setup data

Handling of operation of air to air heat exchanger or ventilating fan

 

 

￿￿￿￿

Unavailable (At shipment)

 

 

￿￿￿￿

Available

 

 

5 Push SET button. (OK if display goes on.)

To change the selected indoor unit, go to the procedure 2 ).

To change the item to be set up, go to the procedure 3 ).

6 Pushing TEST returns the status to the usual stop status.

(2) Wiring

 

 

 

 

Relay (DC12V, procured locally)

 

 

 

CN32

 

 

 

 

 

 

 

 

 

 

 

 

Outside control

 

 

1

1

 

 

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

 

 

 

input of fan

 

2

2

 

 

 

 

 

 

 

 

 

(2P WHI)

 

 

 

 

 

 

 

 

 

 

 

 

To terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

Note)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Determine the cable length between the

 

 

 

indoor control P.C. board and the relay within 2m.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compact 4-way Air Discharge Cassette type

4-way Air Discharge Cassette type

1-way Air Discharge Cassette type (2 series)

model :

Concealed Duct Standard type

Slim Duct type

Under Ceiling type

High Wall type

 

Corresponds up to a relay in which rated current of the operation coil is approx. 75mA

Other type models:

Correspond up to a relay in which rated current of the operation coil is approx. 16mA (Does not correspond to a terminal block type relay on the market.)

42

Page 42
Image 42
Toshiba MMU-AP0091MH, MMU-AP0181MH Ventilating fan control from remote controller, Function, Operation, Wiring