Check code name

 

 

Check code name

 

 

Cause of operation

 

 

 

 

[L18]

 

Flow selector unit system error

An indoor unit which has been operated in

 

 

 

 

 

cooling only mode is operated in heating mode

 

 

 

 

 

without setup for cooling only mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Did set up All cooling

 

NO

 

 

Set up All cooling mode.

 

 

 

 

Item code (DN)=OF

to All cooling indoor unit?

 

 

 

 

 

 

 

 

Cooling only operation mode=0001

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check flow selector unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check code name

Check code name

 

Cause of operation

 

 

 

 

[L29]

IPDU quantity error

1.

Incorrect model setup in service for I/F P.C.

 

 

 

board

 

 

2.

Communication error between IPDU, fan

 

 

 

IPDU and I/F

 

 

3.

IPDU, fan IPDU, I/F P.C. board error

 

 

 

 

Auxiliary code :

 

 

 

01: IPDU1 error

02: IPDU2 error

 

 

03: IPDU1, 2 error

04: Fan IPDU error

 

 

05: IPDU1, fan IPDU error

06: IPDU2, fan IPDU error

 

 

07: All IPDU error or disconnection of communication line between IPDU-I/F P.C. board or outdoor I/F P.C. board error

Check code name

Check code name

Cause of operation

 

 

 

[L20]

Duplicated central

Central control addresses are duplicated.

 

control addresses

 

 

 

 

Is jumper setup of outdoor I/F P.C. board correct?

NO

(Jumpers 7, 8, 9 ON)

 

 

YES

 

 

 

 

 

YES

Is communication connector between IPDU and

 

I/F P.C. board connected?

 

 

NO

 

 

 

 

 

 

Correct connection of connector.

Correct connection of connector.

Are not two or more

YES

central control system identical

 

 

network addresses connected?

 

NO

 

80

Correct the network address of the central control system.

Check the network adaptor on the indoor P.C. board.

Is there no disconnection of communication

YES

line between IPDU and I/F P.C. board?

 

 

NO

 

 

 

 

 

 

Is there voltage fluctuation between

NO

4 and 5 pins of CN600 on I/F P.C. board.

 

 

(Measurement by tester: DC0 to 5V, 5 pin GND)

 

 

YES

 

 

 

 

 

 

Replace communication line.

I/F P.C. board error

Check code name

Check code name

 

Cause of operation

 

 

 

 

[L28]

Quantity over of

1.

Quantity over of connected outdoor units

 

connected outdoor units

2.

Connection error of communication line

 

 

 

between outdoor units

 

 

3.

Outdoor I/F P.C. board error

Is there voltage fluctuation between

 

NO

IPDU P.C. board error

3 and 5 pins of CN600 on I/F P.C. board.

 

 

 

 

 

(Measurement by tester: DC0 to 5V, 5 pin GND)

 

 

YES

Both IPDU (No.1, No.2) and fan IPDU

 

 

 

did not return the communication.

 

 

 

 

 

 

Is No. of connected

NO

Max. 3 units are allowed for flex system.

outdoor units below 3 units?

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

NO

 

Is communication line between

 

Correct connection of communication line.

 

 

outdoor units correctly connected?

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor I/F P.C. board.

On the fan power supply P.C. board,

NO

1) CN503: Between 1 and 5 pins 12V

 

2)CN503: Between 2 and 5 pins 7V

3)Between +5V and GND at the side of CN505: 5V

YES

Replace IPDU P.C. board with trouble.

Replace fan power supply P.C. board.

Auxiliary code

P.C. board to be replaced

01

IPDU1

02

IPDU2

 

 

03

IPDU1, 2

 

 

04

Fan IPDU

 

 

05

IPDU1, fan IPDU

 

 

06

IPDU2, fan IPDU

 

 

07

IPDU1, 2, fan IPDU, I/F

 

 