No.

Part name

Procedure

 

 

 

Remarks

 

 

 

 

 

 

 

11

Drain pan

1. Detachment

 

 

 

2 screws

 

 

1) Perform works of procedure

4

-1 and 8

-1.

 

 

 

2)Remove the drain cap and extract drain water accumulated in the drain pan.

NOTE)

Socket of drain pan

When removing the drain cap, be sure to receive

 

drain water with a bucket, etc.

 

3) Take off screws fixing the drain pan to remove

Drain pan

the drain pan. (Ø4×10, 4 pcs.)

 

2.Attachment

1)Insert the drain cap into the drain pan.

NOTE)

 

Put a stick or others into hole at center of the drain

 

cap, and then insert the drain cap until it strikes on

2 screws

the socket of the drain pan.

 

2)Draw each lead wire to the correct positions, and then insert the drain pan into the main unit.

NOTE)

Piping holder rib

 

Draw lead wires of the drain pump and the float switch along the guide of the cabinet. Insert the drain pan along the guides of sensors (TC1, TC2, TCJ) and PMV lead wire.

The drain pan and each lead wire are not caught in; otherwise water leakage may be caused.

3) Fix the drain pan with screws. (Ø4 × 10, 4 pcs.)

Piping holder

Lead wire

12Drain pump 1. Detachment

assembly

1)

Perform work of procedure 11 -1.

Drain pump assembly

 

2)

Pick up the hose band and slide it from the

Hose band

 

 

pump connecting part to remove the drain

 

 

 

 

 

hose.

 

3)Take off screws (Ø4 × 10, 3 pcs.) fixing the drain pump assembly, and then move hooking

claw (1 position) of the main body from the drain pump assembly to remove the drain pump assembly.

2. Attachment

 

1) Fix the drain pump assembly as original.

White marked position

NOTE)

Drain hose

For fixing, use a hooking claw (1 position) and screws (3 positions).

When screwing, be sure not to run on the hooking claw at main body side.

2)Mount the drain hose and the hose band as original.

NOTE)

Insert the drain hose up to the end of pump connect- ing part, and then put the band at white marked position of the hose.

Fixing screw

Hooking claw

for drain pump

for drain pump

105

Page 105
Image 105
Toshiba MMU-AP0181MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, MMU-AP0121MH service manual 105, Drain pump 1. Detachment

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.