Toshiba MMU-AP0071MH Main Outdoor 7-segment display, Check code Auxiliary code, Remote, Detected

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 53
Image 53

53

 

 

Check code

 

 

 

Main

 

Outdoor 7-segment display

remote

 

 

Check code

Auxiliary code

controller

E31

E31

01: IPDU1 error

 

 

02: IPDU2 error

 

 

03: IPDU1, 2 errors

 

 

04: Fan IPDU error

 

 

05: IPDU1 + Fan IPDU error

 

 

06: IPDU2 + Fan IPDU error

 

 

07: All IPDU error or communication error

 

 

between IPDU and I/F P.C. board or

 

 

outdoor I/F P.C. board error

 

 

 

F01

 

 

 

F02

 

 

 

F03

 

 

 

F04

F04

 

 

 

F05

F05

 

 

 

F06

F06

 

 

 

F07

F07

 

 

 

F08

F08

 

 

 

F10

 

 

 

F12

F12

01: TS1

 

 

02: TS2

 

 

 

Detected

Check code name

Status

Error detection condition

Check item (position)

position

 

 

 

 

I/F

IPDU communication

All stop

Communication of each IPDU (P.C. board) in

• Check connection of communication connector and

 

error

 

inverter box interrupted.

disconnection between IPDU and I/F P.C. board.

 

 

 

 

• Check outdoor P.C. board (I/F, IPDU, Fan IPDU) error.

 

 

 

 

• Check external noise.

 

 

 

 

• Check power supply P.C. board for fan error.

Indoor unit

Indoor TCJ sensor

Corresponding

Resistance value of sensor is infinite or zero.

Check connection/cabling of TCJ sensor connector.

 

error

unit only stops.

 

(Open/Short)

• Check characteristics of TCJ sensor resistance value.

 

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

Indoor unit

Indoor TC2 sensor

Corresponding

Resistance value of sensor is infinite or zero

Check connection/cabling of TC2 sensor connector.

 

error

unit only stops.

 

(Open/Short).

• Check characteristics of TC2 sensor resistance value.

 

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

Indoor unit

Indoor TC1 sensor

Corresponding

Resistance value of sensor is infinite or zero

Check connection/cabling of TC1 sensor connector.

 

error

unit only stops.

 

(Open/Short).

• Check characteristics of TC1 sensor resistance value.

 

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

I/F

TD1 sensor error

All stop

Resistance value of sensor is infinite or zero

Check connection of TD1 sensor connector.

 

 

 

 

(Open/Short)

• Check characteristics of TD1 sensor resistance value.

 

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

I/F

TD2 sensor error

All stop

Resistance value of sensor is infinite or zero

Check connection of TD2 sensor connector.

 

 

 

 

(Open/Short)

• Check characteristics of TD2 sensor resistance value.

 

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

I/F

TE1 sensor error

All stop

Resistance value of sensor is infinite or zero

Check connection of TE1 sensor connector.

 

 

 

 

(Open/Short).

Check characteristics of TE1 sensor resistance value.

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

I/F

TL sensor error

All stop

Resistance value of sensor is infinite or zero

Check connection of TL sensor connector.

 

 

 

 

(Open/Short).

Check characteristics of TL sensor resistance value.

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

I/F

TO sensor error

All stop

Resistance value of sensor is infinite or zero

Check connection of TO sensor connector.

 

 

 

 

(Open/Short).

Check characteristics of TO sensor resistance value.

 

 

 

 

 

• Check outdoor P.C. board (I/F) error.

 

 

 

 

 

 

 

Indoor

Indoor TA sensor

Corresponding

Resistance value of sensor is infinite or zero

Check connection/cabling of TA sensor connector.

 

error

unit only stops.

 

(Open/Short).

Check characteristics of TA sensor resistance value.

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

I/F

TS1, TS2 sensor

All stop

Resistance value of sensor is infinite or zero

Check connection of TS1 or TS2 sensor connector.

 

error

 

 

(Open/Short).

Check characteristics of TS1, TS2 sensor resistance value.

 

 

 

 

 

Check outdoor P.C. board (I/F) error.

Page 53
Image 53
Toshiba MMU-AP0071MH, MMU-AP0181MH Main Outdoor 7-segment display, Check code Auxiliary code, Remote, Detected

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.