Toshiba MMU-AP0151MH P19 Way valve operation error, P20 High-pressure protective operation

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 86
Image 86

Check code name

Check code name

Cause of operation

[P19]

4-way valve operation error

1.

4-way valve error

 

 

2.

TS1 sensor/TE1 sensor error

 

 

3.

Pd sensor/Ps sensor error

 

 

4.

TE sensor/TL sensor misconnection

Check code name

Check code name

Cause of operation

[P20]

High-pressure protective operation 1.

Pd sensor error

 

2.

Service valve closed.

 

3.

Indoor/outdoor fan error

 

4.

Indoor/outdoor PMV clogging

 

5.

Indoor/outdoor heat exchanger clogging

 

6.

SV2 circuit error

Auxiliary code : Detected outdoor unit No.

Is 4-way valve coil

NO

connector connected?

 

 

YES

 

 

 

 

 

 

Correct connector connection.

(4-way valve coil: CN317)

Correct connector connection.

7.

SV4 circuit error

8.

SV5 circuit error

9.

Outdoor I/F P.C. board error

10.

Operation error of check valve of main

 

discharge pipe

11.

Refrigerant overcharge

Are TS1, TE1, Pd, Ps sensor

NO

connectors connected?

 

 

 

YES

 

 

 

 

 

 

 

NO

Are characteristics of resistance value

 

of TS1 and TE1 sensors normal?

 

 

 

YES

 

 

 

 

 

 

 

NO

Are output voltage characteristics

 

of Pd and Ps sensors normal?

 

86

 

YES

 

 

 

 

 

NO

 

 

Are connection and installation

 

of TE1 and TL sensors correct?

 

TS1 sensor: CN504

TE1 sensor: CN505 Pd sensor: CN501 Ps sensor: CN500

Replace sensor.

Replace sensor.

Correct connection

and installation.

Are service valves fully opened?

YES

Are characteristics of

high-pressure sensor normal?

YES

Check mispiping of discharge gas/

suction gas main pipes.

Normal

Check operation of PMV3 SV12.

Normal

Is the flow selector unit normal?

Normal

Reset power supply, and start a test operation corresponded to the season.

NO

NO

Abnormal

Abnormal

Abnormal

All cooling operation

To

B

All heating operation

To

C

Open service valves fully.

Check parts.

Failure Replace

Correct piping.

Replace defective parts.

Repair the flow selector unit.

YES

B All cooling operation

1. Pressure by pressure gauge (Check joint)

2.

Pressure display on 7-segment display

3.

Output voltage of I/F P.C. board

 

If 1 and 2, 3 are different, an error of pressure sensor is considered.

Reset the power supply and start heating test operation.

Does cooling outdoor fan normally operate?

YES

Is there no fan crack or coming-off?

If 2 and 3 are different, check I/F P.C. board.

NO

Correct faulty parts.

YES

Correct faulty parts.

Is the flow selector unit normal?

YES

Does 4-way valve operate?

NO

4-way valve error

NO

YES

Does not discharge

NO

refrigerant gas bypass to

 

 

 

 

 

suction side through

 

 

 

4-way valve?

*1

 

YES

Check 4-way valve.

Replace the FS unit.

If an error did not occur in test operation, restart the operation.

NO

Is outdoor PMV1, 2 normal?

YES

Is there a cause to interfere operation of heat exchanger of outdoor unit?

1.Heat exchanger clogging

2.Air short circuit

NO

Is SV2 circuit normal?

YES

Is SV4 circuit normal?

(Connector connection, fan IPDU, fan motor, wiring)

NO

Correct faulty position.

(Connector connection wiring, coil mounting, valve clogging, etc)

YES

Eliminate the interfered causes.

NO

Repair SV2 circuit.

(Coil error, clogging, disconnection of cable, etc.)

NO

Repair SV4 circuit.

*1 Check TS and TE temperature of the outdoor unit which compressors is operated.

(I/F) SW01=[1], SW02=[6], SW03=[2]

TS sensor temperature

SW01=[1], SW02=[7], SW03=[2]

ÆTE sensor temperature

<Judgment criteria>

TE sensor: Normal if TE 20˚C except summer season (Outside temp 20˚C or lower)

TS sensor: Normal if TS 40˚C except summer season (Outside temp 20˚C or lower)

YES

Does check valve of main

discharge pipe normally operate?

YES

Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition

(Coil error, clogging, disconnection of cable, etc.)

NO

Repair check valve. Replace

Page 86
Image 86
Toshiba MMU-AP0151MH P19 Way valve operation error, P20 High-pressure protective operation, Judgment criteria

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.