Toshiba MMU-AP0181MH, MMU-AP0151MH Leakage check for SV3C valve, Clogging for SV3E valve

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 75
Image 75

Check code name

 

Check code name

 

 

 

Cause of operation

 

 

 

 

 

 

 

 

 

[H07]

 

Oil level down

1. Valves of balance pipes closed.

 

 

 

detection protection

2. Miscabling or misinstallation of TK1 to TK4 sensors

 

 

 

 

3.

TK1 to TK4 sensor error

 

 

 

 

 

4.

Gas leak or oil leak of all outdoor units

 

 

 

 

 

5.

Refrigerant stagnation of compressor case

 

 

 

 

 

6.

SV3A, 3B, 3D, 3C, 3E valve error

 

 

 

 

 

7.

Clogging of oil return circuit from oil separator

 

 

 

 

 

8.

Clogging of oil-equation circuit system

 

 

 

 

 

 

 

 

 

Are TK1, TK2, TK3, and

 

NO

 

 

 

 

 

 

 

 

Correct miswiring and misinstallation.

TK4 sensors connected correctly?

 

 

 

 

TK1: CN514, TK2: CN515

)

 

 

 

Is there no sensor coming-off or misinstallation?

 

 

 

( TK3: CN516, TK4: CN523

YES

In some cases, it may be difficult to check the leakage of clogging in the following condition of refrigerant stagnation in low ambient temperature condition.

In this case, take a longer operating time prior to check.

(Criterion: Discharge temperature of TD1 and TD2 are 60°C or higher)

(*1)

a)

Leakage check for SV3A valve (For multiple outdoor unit system)

 

Turn off the power supply, take off connector of SV3A valve, and then start a test operation after power-ON.

 

Check the temperature change at secondary side of SV3A valve during operation . (in the figure.)

 

 

If temperature is raised, it is a leakage of SV3A valve. Replace SV3A valve.

b)

Leakage check for SV3C valve

 

Turn off the power supply, take off connector of SV3C valve, and then start a test operation after power-ON.

 

After operation for several minutes, check temperature at secondary side of SV3C valve. (in the figure.)

 

 

If temperature is high (equivalent to discharge temperature TD), it is a leakage of SV3C valve. Replace

 

 

SV3C valve.

Are TK1 and TK2 sensors connected correctly? Is there no sensor coming-off or misinstallation?

Are sensor characteristics normal?

YES

Check leakage of SV6 circuit.

Normal

NO

Characteristics-2

Abnormal

Correct miswiring and misinstallation.

(TS1: CN504, TS2: CN522)

Sensor error Replace

Replace defective parts.

(Even if there is leakage from SV3C valve does not occur, temperature of SV3C valve at secondary side

rises during operation. When the checked temperature is equivalent to TD temperature, it is a leakage of

SV3C valve. Replace SV3C valve.)

c) Clogging check for SV3B valve (For multiple outdoor unit system)

• While outdoor unit is operated, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr] [ 2], and push SW04

for 2 seconds or more.

75

Check whether there is setup missing

 

 

 

Abnormal

Set up to cooling only operation mode.

 

 

 

 

 

 

Item code (DN) OF

of cooling only indoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling only operation mode: 0001

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

NO

 

 

 

Are characteristics of TK1 to TK4 normal?

 

 

 

 

 

 

 

 

 

Characteristics-4

 

Sensor error Replace

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check gas leak of outdoor unit.

 

 

 

Abnormal

Specify a position where

Check oil stain in the

 

 

 

 

 

 

 

gas leaked and repair it.

 

 

 

 

 

 

 

( machine room of outdoor unit. )

 

 

 

 

 

 

 

(Recharge, refill oil.)

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

Is the flow selector unit normal?

 

 

 

 

 

 

Repair the flow selector unit.

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check accumulation of

 

NO

 

 

 

( 1) Check leakage of

YES

 

 

 

 

 

solenoid valve. (SV3C)

 

 

Replace defective parts

refrigerant in compressor case.

 

 

 

 

Check clogging.

 

 

 

Refrigerant accumulation

 

 

 

(SV3E)

 

 

 

 

 

 

 

 

No leakage or clogging

 

 

 

 

 

 

 

 

 

Correct accumulation of

 

 

 

 

 

 

 

 

 

 

 

refrigerant in compressor case,

 

 

 

 

 

 

 

 

 

 

 

reset power supply and

 

 

 

 

 

( 2) Check clogging in oil

 

 

 

then start operation.

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

recovery circuit of the oil separator.

 

 

Replace defective parts

 

 

 

 

 

 

 

 

(Capillary, Strainer)

 

 

 

 

 

 

 

 

 

 

 

Check clogging of SV3D valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check oil level judgment

 

 

 

 

 

 

No clogging

 

 

 

of each compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW01/02/03=1/16/1

are

 

 

 

 

 

 

 

displayed on 7-

segment display.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are all the oil levels appropriate?

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

Clogging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eliminate cause of accumulation.

 

 

 

 

 

Check clogging of oil-equation circuit.

 

 

Replace defective parts

 

 

 

 

 

( 3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor/outdoor PMV error

(Cause of refrigerant accumulation) Discharge check valve error, etc.

• Set up SW02 = [9], and turn on SV3A, SV3B, SV3C valves. (7-segment display [Hr] [ 3–])

• While outdoor unit is operating, check temperature change at secondary side of SV3B valve. (ƒ in the figure.)

If temperature does not rise (equivalent to suction temperature), it is a clogging of SV3B valve.

Replace SV3B valve.

d) Clogging for SV3E valve

Reset the power supply.

ò

Referring to “Valve forced open/close function” of the outdoor unit, check ON/OFF operation (Sound, coil surface temp up) of SV3E valve is performed.

ò

Start test operation in COOL or HEAT mode.

ò

After operation for several minutes, check the pipe temperature at the secondary side of SV3E valve whether temperature changes or not. If it is equivalent to outside temperature, clogging of SV3E is considered.

(in the figure.)

(Reference)

If SV3E valve is clogged, temperature of all TK1, TK2, TK3, and TK4 do not change.

(*2) Clogging check for SV3D valve of oil return circuit from oil separator

a)Oil return circuit

While outdoor unit is operating, check temperature (secondary side of capillary) on oil return circuit. (in the figure.)

If temperature is low equivalent to suction temperature), a clogging of strainer of oil return circuit or capillary is considered. Repair the clogged part.

b)Clogging check for SV3D valve

While outdoor unit is operating, set up SW01/02/03 = [2] [1] [3] to 7-segment display [Hr] [ 2], and push SW04 for 2 seconds or more.

Set up SW02 = [6], and turn on SV3D valve. (7-segment display [Hr] [ 3d])

If temperature is low at secondary side of the valve or it does not change, clogging of valve, capillary, or strainer is considered. (in the figure.)

(Reference) If refrigerant is accumulated in the compressor case, oil level short may be judged.

Page 75
Image 75
Toshiba MMU-AP0181MH, MMU-AP0151MH Leakage check for SV3C valve, Clogging for SV3E valve, Clogging check for SV3D valve

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.