Toshiba MMU-AP0071MH P26 Tr short-circuit protection error, P29, P31, Compressor position

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 88
Image 88

Check code name

Check code name

Cause of operation

[P26]

G-Tr short-circuit protection error 1.

Outdoor unit power error

 

2.

IPDU error/Cable connection error

 

3.

Compressor error

 

4.

IPDU P.C. board error

Check code name

Check code name

 

Cause of operation

 

 

 

 

[P29]

Compressor position

1)

Cable/connector connection error

 

detective circuit error

2)

Compressor error

 

 

3)

IPDU P.C. board error

 

 

 

 

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

NO

Is power voltage of outdoor unit normal?

 

YES

 

 

 

NO

Is wire connector connection

 

on IPDU P.C. board normal?

 

 

YES

 

 

 

 

 

NO

Is compressor normal?

 

 

 

YES

 

 

 

 

 

NO

Is smoothing condenser normal?

 

(1500µF, 350V)

 

Correct power line.

Correct connection of wire connector.

Replace compressor.

Check capacity coming-out/

external appearance.

Are connector connection

NO

 

and wiring normal?

 

 

YES

 

 

 

 

 

YES

Is not grounded?

 

 

 

NO

 

 

 

 

 

YES

Is not winding shorted?

 

(Is winding resistance 0.1 to 0.3 ?)

 

 

NO

 

 

 

 

 

 

YES

Is not winding opened?

NO

Check and correct circuit and cables such as cabling to compressor, etc.

Compressor error Replace

Compressor error Replace

Compressor error Replace

88

YES

Replace IPDU P.C. board.

Check IPDU P.C. board.

Failure Replace

Check code name

Check code name

Cause of operation

 

 

 

[P31]

Other indoor error

Other indoor unit in the group is abnormal.

 

(Group follower unit error)

 

 

 

 

When the header unit of the group detected [E03, L03, L07, L08 error], the follower unit of the group displays [P31] error and stops. There are no check code display and alarm record of the main remote controller.

Page 88
Image 88
Toshiba MMU-AP0071MH P26 Tr short-circuit protection error, P29, P31, Compressor position, Detective circuit error