Check code name | Check code name | Cause of operation |
[H04] | Compressor 1 case thermo operation 1. Case thermo circuit error | |||
[H14] | Compressor 2 case thermo operation | 2. | I/F P.C. board error | |
3. | Service valve closed | |||
|
| |||
|
| 4. | Outdoor PMV clogging | |
|
| 5. | SV4 valve leak, Coil misinstallation | |
|
| 6. | ||
|
| 7. | Compressor error | |
|
| 8. | Refrigerant shortage |
Check code name | Check code name | Cause of operation |
[H06] |
| 1. Service valve close | |
|
| 2. | Ps sensor error |
|
| 3. | SV2, SV4 circuit error |
|
| 4. | Miscabling of communication between |
|
|
| indoor and outdoor |
|
| 5. | Indoor/outdoor fan and condenser error |
|
| 6. | Indoor/outdoor PMV clogging |
|
| 7. | Indoor/outdoor heat exchanger clogging |
|
| 8. | Refrigerant shortage |
Is case thermo circuit normal?
1.Connector connection
2.Wiring
3.I/F P.C. board (Note 1)
YES
Are service valves of
gas pipe and liquid pipe of outdoor unit fully opened?
NO
(Note 1)
1.Case thermo is usually closed.
2.Operation temperature of case thermo is 120˚C.
NO
Repair case thermo circuit.
Open service valves fully.
Are service valves of gas and
liquid pipe of outdoor unit fully opened?
YES
Are characteristics of
YES
NO
Open service valves fully.
NO
Exchange
1 Pressure by pressure gauge (Check joint)
2Pressure display on
3Output voltage of I/F P.C. board
If 1 and 2, 3 are different, an error of pressure sensor error is considered. If 2 and 3 are different, check I/F P.C. board.
74
YES
Are outdoor PMV1/2/3 normal? 1. Connector connection
2. Wiring | 3. Coil |
4. Valve body | 5. I/F P.C. board |
| YES |
|
Operation starts.
Are SV41 and SV42
Valve circuits normal?
1.Misinstallation installation and connector connection of SV41 and SV42
2.Leakage from SV41, 42 circuit
YES
Does not refrigerant
bypass from discharge of
suction through
NO
Is not refrigerant bypassed from discharge to suction?
NO
Is compressor normal? (Note 2)
NO
Connector CN300, 301, White
NO
SV4 valve: Connector CN311, Blue
YES
YES
NO
Repair outdoor PMV.
Correct SV4, SV5, SV11
valve circuits.
Check
Check piping.
Compressor error
|
| Are SV2 and SV4 circuits normal? |
| NO |
| Correct SV2 and SV4 circuits. | ||||||||||
|
|
| Check miscabling, misinstallation and |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| YES |
| connector connection. |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| ||||||
| Is there no mispiping of discharge gas |
| YES |
|
|
|
|
| ||||||||
|
|
|
|
| Correct piping. | |||||||||||
|
|
| and suction gas main pipes? |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Is not indoor unit with different circuit connected? |
| YES |
|
|
| Correct cabling. | ||||||||||
|
|
| (Check with miscabling check |
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| NO |
|
|
| function of outdoor unit.) |
|
|
|
|
| ||
|
|
|
| Is flow selector normal? |
| NO |
|
|
| Check flow selector. | ||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| In cooling season, go to (A), In heating season, go to (B) | ||||||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
| (A) Cooling |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Are following items concerned |
|
|
|
|
| |
|
|
|
| Does indoor fan normally | NO |
|
| to indoor fan motor normal? |
| NO |
|
| ||||
|
|
|
|
|
| 1. Connector connection |
|
|
| Repair faulty parts. | ||||||
|
|
|
| operate in cooling season? |
|
|
| 2. Condenser |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
| YES |
|
|
| 3. Motor |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| 4. Fan |
|
|
|
|
| ||
|
| YES |
|
|
|
|
|
|
|
|
|
| ||||
Cleaning |
|
|
| Is there clogging of indoor |
|
|
|
| YES |
|
|
| Check indoor P.C. board. | |||
|
|
| air filter or heat exchanger? |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
| NO | NO |
|
| Is connector connection |
| NO | Failure Replace | |||
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
| Is indoor PMV normal? |
|
|
|
|
| |||||||
|
|
|
|
|
|
| or coil normal? |
|
|
| Repair faulty parts. | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| YES |
|
|
|
| YES |
| YES |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
| Refrigerant shortage or |
|
|
| Is there clogging on whole valve? |
|
|
| Replace PMV body. | ||||
|
|
|
| clogging or pipe deformed |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (B) Heating |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| NO |
|
| |
|
|
|
| Is outdoor fan normally | NO |
|
| Is indoor fan system normal? |
| Check outdoor |
YES | (Note 2) Check the following items mainly. |
| 1. Existence of abnormal sound and abnormal vibration during operation at start time |
operated in heating season? |
| • Fan crack |
| I/F P.C. board. |
|
| |||
| • Fan |
| Failure Replace | |
|
|
|
2. | Abnormal overheat of case during operation or stop (Never touch with hands.) | |||
3. | Current of compressor lead during operation or starting (No rapid current change) | |||
| YES |
| ||
Is flow selector unit normal? | Check flow selector unit. | |||
|
| |||
|
Cleaning
YES
YES
Is there clogging of
outdoor heat exchanger?
YES
Repair faulty parts.
NO |
Refrigerant shortage, |
NO
Is outdoor PMV normal?
YES
NO
clogging, pipe breakage | (After checking there is no slogging or pipe breakage, charge refrigerant again.) |
|
Refrigerant shortage,
clogging, pipe deformed