Toshiba MMU-AP0121MH, MMU-AP0181MH, MMU-AP0151MH H06 Low-pressure protective operation

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 74
Image 74

Check code name

Check code name

Cause of operation

[H04]

Compressor 1 case thermo operation 1. Case thermo circuit error

[H14]

Compressor 2 case thermo operation

2.

I/F P.C. board error

3.

Service valve closed

 

 

 

 

4.

Outdoor PMV clogging

 

 

5.

SV4 valve leak, Coil misinstallation

 

 

6.

4-way valve error

 

 

7.

Compressor error

 

 

8.

Refrigerant shortage

Check code name

Check code name

Cause of operation

[H06]

Low-pressure protective operation

1. Service valve close

 

 

2.

Ps sensor error

 

 

3.

SV2, SV4 circuit error

 

 

4.

Miscabling of communication between

 

 

 

indoor and outdoor

 

 

5.

Indoor/outdoor fan and condenser error

 

 

6.

Indoor/outdoor PMV clogging

 

 

7.

Indoor/outdoor heat exchanger clogging

 

 

8.

Refrigerant shortage

Is case thermo circuit normal?

1.Connector connection

2.Wiring

3.I/F P.C. board (Note 1)

YES

Are service valves of

gas pipe and liquid pipe of outdoor unit fully opened?

NO

(Note 1)

1.Case thermo is usually closed.

2.Operation temperature of case thermo is 120˚C.

NO

Repair case thermo circuit.

Open service valves fully.

Are service valves of gas and

liquid pipe of outdoor unit fully opened?

YES

Are characteristics of low-pressure sensor normal?

YES

NO

Open service valves fully.

NO

Exchange low-pressure sensor.

1 Pressure by pressure gauge (Check joint)

2Pressure display on 7-segment display

3Output voltage of I/F P.C. board

If 1 and 2, 3 are different, an error of pressure sensor error is considered. If 2 and 3 are different, check I/F P.C. board.

74

YES

Are outdoor PMV1/2/3 normal? 1. Connector connection

2. Wiring

3. Coil

4. Valve body

5. I/F P.C. board

 

YES

 

Operation starts.

Are SV41 and SV42

Valve circuits normal?

1.Misinstallation installation and connector connection of SV41 and SV42

2.Leakage from SV41, 42 circuit

YES

Does not refrigerant

bypass from discharge of

suction through 4-way valve?

NO

Is not refrigerant bypassed from discharge to suction?

NO

Is compressor normal? (Note 2)

NO

Connector CN300, 301, White

NO

SV4 valve: Connector CN311, Blue

YES

YES

NO

Repair outdoor PMV.

Correct SV4, SV5, SV11

valve circuits.

Check 4-way valve.

Check piping.

Compressor error

 

 

Are SV2 and SV4 circuits normal?

 

NO

 

Correct SV2 and SV4 circuits.

 

 

 

Check miscabling, misinstallation and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

connector connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there no mispiping of discharge gas

 

YES

 

 

 

 

 

 

 

 

 

 

Correct piping.

 

 

 

and suction gas main pipes?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is not indoor unit with different circuit connected?

 

YES

 

 

 

Correct cabling.

 

 

 

(Check with miscabling check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

function of outdoor unit.)

 

 

 

 

 

 

 

 

 

Is flow selector normal?

 

NO

 

 

 

Check flow selector.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In cooling season, go to (A), In heating season, go to (B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A) Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are following items concerned

 

 

 

 

 

 

 

 

 

Does indoor fan normally

NO

 

 

to indoor fan motor normal?

 

NO

 

 

 

 

 

 

 

 

1. Connector connection

 

 

 

Repair faulty parts.

 

 

 

 

operate in cooling season?

 

 

 

2. Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

3. Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Fan

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Cleaning

 

 

 

Is there clogging of indoor

 

 

 

 

YES

 

 

 

Check indoor P.C. board.

 

 

 

air filter or heat exchanger?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

NO

 

 

Is connector connection

 

NO

Failure Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is indoor PMV normal?

 

 

 

 

 

 

 

 

 

 

 

 

or coil normal?

 

 

 

Repair faulty parts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

YES

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant shortage or

 

 

 

Is there clogging on whole valve?

 

 

 

Replace PMV body.

 

 

 

 

clogging or pipe deformed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(B) Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

Is outdoor fan normally

NO

 

 

Is indoor fan system normal?

 

Check outdoor

YES

(Note 2) Check the following items mainly.

 

1. Existence of abnormal sound and abnormal vibration during operation at start time

operated in heating season?

 

• Fan crack

 

I/F P.C. board.

 

 

 

• Fan coming-off

 

Failure Replace

 

 

 

2.

Abnormal overheat of case during operation or stop (Never touch with hands.)

3.

Current of compressor lead during operation or starting (No rapid current change)

 

YES

 

Is flow selector unit normal?

Check flow selector unit.

 

 

 

Cleaning

YES

YES

Is there clogging of

outdoor heat exchanger?

YES

Repair faulty parts.

NO

Refrigerant shortage,

NO

Is outdoor PMV normal?

YES

NO

clogging, pipe breakage

(After checking there is no slogging or pipe breakage, charge refrigerant again.)

 

Refrigerant shortage,

clogging, pipe deformed

Page 74
Image 74
Toshiba MMU-AP0121MH, MMU-AP0181MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH H06 Low-pressure protective operation