Toshiba MMU-AP0121MH, MMU-AP0181MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH Drain Piping Work

Models: MMU-AP0181MH MMU-AP0071MH MMU-AP0091MH MMU-AP0151MH MMU-AP0121MH

1 117
Download 117 pages 2 Kb
Page 24
Image 24

4 DRAIN PIPING WORK

CAUTION

Install the drain piping so that the water drains effectively.

Apply heat insulation to prevent dew condensation from forming.

Incorrectly installed pipe work may result in a water leak.

Pipe material/Insulator and size

The following materials for piping work and insulation are to be procured locally.

 

Hard vinyl chloride pipe socket for VP25

Pipe material Hard vinyl chloride pipe VP25

 

(Outer diameter Ø32 mm)

 

 

Insulator

Foamed polyethylene foam, thickness:

10 mm or more

 

Connection of drain pipe

Connect the hard socket (Procured locally) to the hard socket side of the supplied flexible hose which has been installed.

Connect the drain pipes (Procured locally) in turn to the connected hard sockets.

REQUIREMENT

Check the draining

After completion of drain piping,

Check water drains away and that no water leaks from any of the connecting parts. At the same time check for any abnormal sounds from the drain pump.

Ensure drainage is checked during cooling mode.

When the electric work has finished:

• Before installing the ceiling panel, pour water as

REQUIREMENT

• Using an adhesive agent for vinyl chloride,

connect the hard vinyl chloride pipes so that

water does not leak.

shown in the following figure, check water drains

from the drain pipe connecting port (Transparent) in

• Ensure insulating of the drain pipes and connecting parts on the indoor units.

• The drain pipe should have a downward slope of at least 1/100 and ensure there are no swells or blockages as this will cause abnormal sounds.

• The maximum traverse length of drain pipe is 20 m. Provide support brackets at intervals of 1.5 to 2 m where necessary to prevent movement.

• Install the combined piping as shown in the illustration.

• Do not create an air purge in the pipework, as the water would leak from this point.

As long as possible (10cm)

1.5m to 2m

Support

 

bracket

1/100 or more

Heat downward insulator

Arched

shape NO

GOOD

Trap

• Allow sufficient time for the adhesive to set and

harden. (Refer to the instructions of the

adhesive.)

Drain up

When it is not possible to achieve a natural downward slope on the drain pipe, you can create a vertical lift

COOL mode and then check there are no water

leaks from the drain pipes.

When the electric work has not finished:

Pull out the float switch connector (3P: Red) from

 

P.C. board connector (CN34: Red) of the electric

 

parts box. (Ensure the power is turned off.)

Connect the single-phase 220-240V, 1N, 50Hz (or

 

220V, 1N, 60Hz) power to the terminal blocks R (L)

 

and S (N). (Never apply 220-240V to (A), (B), (U1)

VP25

VP25

VP25

(Collective pipes)

(Drain up) on the pipe.

• Set the height of the drain pipe within 850 mm from

the bottom surface of the ceiling.

and (U2).)

• Pour water referring to the next page figure.

(Amount: 1500 cc to 2000 cc)

24

The hard vinyl-chloride pipe cannot be connected

directly to the drain pipe connecting port of the indoor unit. For connection with the drain pipe connecting port, ensure that the supplied flexible hose is fitted.

Adhesive agent cannot be used for the pipe connecting port (hard socket) on the indoor unit.

Be sure to use the supplied hose band for fixing, otherwise there is a risk of damage or water leakage from the drain pipe connecting port.

 

VP30 or more

 

 

 

 

Downward slope

 

 

 

 

 

 

 

 

 

 

 

 

1/100 or more

 

Drain pipe connecting port

 

VP25 vinyl chloride pipe

(Hard socket)

 

 

 

 

 

 

 

(Procured locally)

 

Attached hose band

Attached flexible hose

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket for VP25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Soft socket

 

 

 

Hard socket

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Procured locally)

Adhesive agent prohibited

 

 

 

The drain pipe should be piped from the drain pipe

 

connecting port horizontally for a maximum of

 

300 mm and then piped vertically.

After piping the vertical lift, ensure the pipe work is

 

set to a downward gradient.

 

 

Rising up orless

 

or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the power is turned on, the drain pump motor

 

drives automatically. Check water is drained from

 

the drain pipe connecting port (Transparent), and

 

then check there is no water leak from the drain

 

pipes.

After checking for water leaks on the drain, turn off

 

the power supply, and re-attach the float switch

 

connector to the original position (CN34) on the P.C.

 

board and refit the electric parts box.

Connection of flexible hose

NO GOOD

max 45˚

627.5mm

850mm

 

up

220–240V, 1N ~, 50Hz 220V 1N ~, 60Hz

R(L) S(N)

Insert the soft socket of the supplied flexible hose

 

into the connecting port of the drain pipe.

Align the supplied hose band to the pipe connecting

 

port end, and tighten.

OK

Riser (Trap)

300mm

Rising

or less

 

 

White

CN34

Red

(RED)

Black

 

max

90˚ Bend

45˚

 

Indoor unit

Underneath of ceiling

Pull out connector CN34 (Red) from P.C. board.

Black

REQUIREMENT

Fix the soft socket with the supplied hose band, tighten at the upper position of the unit.

The supplied flexible hose can bend up to a maximum of 45°

Drain pipe connecting port (Transparent)

Indoor unit body

Align the attached hose band to the end of hose, set the tightening position upward, and then tighten it.

Flexible hose

VP25 vinyl chloride pipe

(Accessory)

(To be local procure)

 

 

 

 

 

 

Socket for VP25 vinyl chloride pipe (To be local procure)

Page 24
Image 24
Toshiba MMU-AP0121MH, MMU-AP0181MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH service manual Drain Piping Work

MMU-AP0181MH, MMU-AP0071MH, MMU-AP0091MH, MMU-AP0151MH, MMU-AP0121MH specifications

The Toshiba MMU-AP series, consisting of models MMU-AP0121MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0071MH, and MMU-AP0181MH, represents a significant advancement in the realm of power management and energy efficiency for a variety of applications. These modules are designed to optimize performance while ensuring minimal energy consumption, making them suitable for both commercial and industrial uses.

One of the standout features of the MMU-AP series is its intelligent power management technology. This feature allows for adaptive energy distribution based on real-time demands. By leveraging precise control algorithms, the modules can adjust their output to match the specific requirements of connected devices, ultimately leading to reduced power loss and increased efficiency. This adaptability not only benefits end-users by lowering operational costs but also contributes to a greener environment by minimizing waste.

The versatility of the MMU-AP series is evident in its wide range of operational capabilities. These power modules are designed to work effectively in various voltage levels and load conditions. With input voltage ranges suitable for standard industrial environments, they can easily be integrated into existing systems, enhancing overall functionality without requiring extensive modifications.

Moreover, the compact design of the MMU-AP modules is another notable characteristic. Their size and light weight facilitate easier installation and integration into tight spaces, making them ideal for applications where real estate is a premium. This compact profile does not compromise performance, as these modules are engineered to deliver robust power output while maintaining thermal efficiency.

In terms of reliability, the MMU-AP series is built with high-grade components that withstand harsh operating conditions. With features such as over-voltage protection, short-circuit protection, and thermal shutdown capabilities, users can trust that their equipment would operate safely and efficiently, thereby extending the lifespan of both the power modules and the devices they serve.

Finally, Toshiba’s commitment to innovation ensures that the MMU-AP series incorporates cutting-edge technology. The series supports communication protocols that enable seamless integration with smart systems, paving the way for advanced monitoring and control functions. This levels up the user experience, providing insights into performance and diagnostics that are crucial for uptime and reliability in demanding environments.

In conclusion, the Toshiba MMU-AP series offers a blend of efficiency, adaptability, and advanced technology, making it a valuable asset for various industrial and commercial applications. Its intelligent design and robust features ensure that users can optimize energy use while maintaining high performance and reliability.