[P12 error]

[P12 error]

Turn off the power.

Is there no connection error or

YES

disconnection on connectors CN333

 

 

and CN334 of indoor unit

 

P.C. board (MCC-1402)?

 

 

 

NO

 

 

 

 

 

 

 

Remove connectors CN333 and CN334

 

of indoor unit P.C. board (MCC-1402).

 

 

 

 

 

 

 

Correct connection

of connector.

CN333

– 101 – CN334

Does the fan rotate without trouble when handling the fan with hands?

YES

Are resistance values

between phases at fan motor connector CN333 motor side of indoor P.C. board (MCC-1402) correct? 1

NO

Incorrect

Replace indoor fan motor.

Replace indoor fan motor.

Correct

1

Are not coil windings between ￿ (Red lead) and ￿ (White lead), between ￿ (White lead) and ￿ (Black lead),

between ￿ (Black lead) and ￿ (Red lead) opened or shorted? The resistance should be the resistance value below.

SM56, SM80 Approx. 70 to 100

SM110, SM140, SM160 Approx. 27 to 40

• Is not grounded between cabinet and ￿, ￿, ￿. It should be 10Mor more.

Is resistance value of

Incorrect

 

Replace indoor fan motor.

 

fan motor connector CN334 motor side

 

 

 

 

 

 

of indoor P.C. board correct? 2

 

 

 

 

 

 

 

 

 

 

Correct

2

Resistance value confirmation of the fan motor position detection circuit

Is not status between ￿ (Yellow lead) and ￿ (Pink lead) opened or shorted? The resistance should be approx. 5k to 20k.

Is output of

NO

indoor fan motor position

 

 

detection signal correct? 3

 

Replace indoor fan motor.

YES

3

Confirmation of the fan motor position detection signal

Using a voltage tester, measure voltage between CN334 ￿ and ￿ on the indoor P.C. board

(MCC-1570) under condition that CN333 and CN334 are mounted and the power supply is turned on. When rotating the fan slowly with hands, the pin voltage should shake between 0 and 5V.

Between ￿ and ￿: 5V

Check indoor P.C. board.

Defect Replace

– 101 –

Page 101
Image 101
Toshiba RAV-SM1603ATZG-E, RAV-SM1603DT-A, RAV-SM1603ATZ-E, RAV-SM1403DT-A service manual P12 error, 101