6-10. Branch Pipe

6-10. Branch Pipe

nTwin system

Now the refrigerant pipe is installed using branch pipes supplied as accessories.

Bend and adjust the refrigerant piping so that the branch pipes and pipe after branching become horizontal.

Fix the branch pipes onto a wall in a ceiling or onto a column.

Provide a straight pipe longer than 500mm in length as the main piping of the branches.

OKOK

Horizontal

Horizontal

500mm or more

NO GOOG

NO GOOG

Inclination

Inclination

6-11. Distributor

nTriple system

Now the refrigerant pipe is installed using distributor supplied as accessories.

Bend and adjust the refrigerant piping so that the distributor and pipe after branching become horizontal.

Fix the distributor onto a wall in a ceiling or onto a column.

Provide a straight pipe longer than 500 mm in length as the main piping of the branches.

<How to install distributor>

Branch pipes are horizontal

Branch pipes are horizontal

and collective pipes are vertical

and collective pipes are vertical

Branch pipes and

Branch pipes and

collective pipes are horizontal

collective pipes are horizontal

Branch pipe

Branch pipe

Collective pipe

Collective pipe

<Gas pipe side>

<Liquid pipe side>

<Restrictions in length of the straight area of the branch pipe (main pipe side)>

Provide a straight area of 500 mm or more on the main pipe side of the branch pipe (for both gas pipe and liquid pipe sides).

 

 

NO GOOG

 

 

Tilt

500 mm or more

500 mm or more

Be sure to install the pipes

horizontally after branching.

 

nAir Purging