6-7. Tolerance of Pipe Length and Pipe Head

6-7. Tolerance of Pipe Length and Pipe Head

n Twin system

 

 

Total length (L + a or L + b)

 

50 m

 

Pipe length

 

 

 

 

Branch pipe length (a, b)

 

15 m

 

(one way)

 

 

 

 

 

Refrigerant pipe

Maximum difference between indoor units

 

10 m

 

 

 

 

(b – a, or a - b)

 

 

 

 

 

specification

 

 

 

 

 

 

 

Between indoor units ( h)

 

0.5 m

 

 

 

 

Height

 

 

 

 

 

 

Between indoor unit

 

When outdoor unit heigher

(H)

30 m

 

difference

 

 

 

 

 

 

 

 

 

and outdoor unit

 

When outdoor unit lower

(H)

30 m

 

 

 

 

 

 

 

 

Number of bent portions

 

10 m or less

 

 

 

 

 

 

 

Indoor unit A

Indoor unit B

n Twin systemh

Distributor

b

a

Branch pipe

Branch pipe

L

Main pipe

H

Outdoor unit

CAUTION

When planning a layout for Units A and B, comply with the following:

1.The lengths after branching (“a” and “b”) should be equal if feasible.

Install Units A and B so that the difference of the branching lengths becomes less than 10m if the lengths cannot be equal due to the branch pipe position.

2.Install Units A and B on the same level.

If Units A and B cannot be installed on the same level, the difference in level should be limited to 0.5m or less.

3.Be certain to install Units A and B in the same room.

Units A and B cannot be operated independently each other.

– 46 –