[P29 error]

[P29 error]

Are connections of

NO

 

cable/connector normal?

 

 

 

YES

 

 

 

 

 

Check and correct circuit cabling such as cabling to compressor.

Is compressor normal?

YES

NO

YES

 

 

Is not earthed?

 

 

NO

 

 

Is not winding shorted?

YES

 

 

(Is resistance between windings 0.6 to 1.2?)

 

 

NO

 

 

YES

 

 

Is not winding opened?

 

 

NO

 

 

 

 

 

 

 

 

 

Check IPDU P.C. board.

 

 

 

Compressor error Replace

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[F06 error]

Are connections of TE/TS sensor

connectors of CDB CN604/CN605 normal?

YES

Are characteristics of TE/TS sensor resistance values normal?

YES

Check CDB.

Defect Replace

[P04 error]

Is connection of TD sensor connector

of CDB CN600 normal?

YES

Are characteristics of TD sensor resistance value normal?

YES

NO

Correct connection of connector.

NO[F06 error][P04 error] Replace TE and TS sensors.

Refer to relational graph of temperature sensor resistance value and temperature Characteristics-3.

NO

Correct connection of connector.

NO

Replace TD sensor.

Check control P.C. board.

Defect Replace

Refer to relational graph of temperature sensor resistance value and temperature Characteristics-4.

– 105 –

Page 105
Image 105