Toshiba RAV-SM1403DT-A service manual 55, Item, Outline of specifications, Remarks, <Cool>, <Heat>

Models: RAV-SM1403DT-A RAV-SM1603ATZ-E RAV-SM1603ATZG-E RAV-SM1603DT-A

1 157
Download 157 pages 61.3 Kb
Page 55
Image 55
<COOL>

No.

Item

Outline of specifications

Remarks

 

 

 

 

6

Air speed selection 1)

Operation [HH], [L] or [AUTO] is performed by command

 

 

 

from the remote controller.

 

 

2)

The air speed is varied with difference between Ta and

HH > L > UL

 

 

Ts while the air speed is set to [AUTO].

 

<COOL>

 

Ta (˚C)

Cooling in

Normal

Cooling/Heating

cooling

[AUTO]

 

HH

HH

(High wind)

(High wind)

+1.5

 

HH

HH

(High wind)

(High wind)

+1.0

 

HH

HH

(High wind)

(High wind)

+0.5

 

L

HH

(Low wind)

(High wind)

Tsc

L

L

(Low wind)

–0.5

 

<HEAT>

 

Ta (˚C)

Cooling in

Normal

Cooling/Heating

heating

[AUTO]

 

 

 

 

 

 

UL (Ultra low wind) only

 

 

 

+0.5

 

 

during compressor-OFF

 

 

 

 

 

L

 

L

 

 

 

 

 

 

 

 

 

 

Tsc

 

(Low wind)

 

(Low wind)

 

 

 

 

 

 

 

 

 

 

 

 

L

 

HH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(High wind)

 

 

 

–0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HH

 

HH

 

 

 

 

 

 

 

 

 

 

–1.0

 

(High wind)

 

(High wind)

 

 

 

 

 

 

 

 

 

 

 

 

HH

 

HH

 

 

 

 

 

 

 

 

 

 

–1.5

 

(High wind)

 

(High wind)

 

 

 

 

 

 

 

 

 

 

 

 

HH

 

HH

 

 

 

 

 

 

 

 

 

 

 

 

 

(High wind)

 

(High wind)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3)

If thermostat is turned off during heating operation, the

STOP operation is the

 

 

mode changes to [UL] or [STOP].

 

 

 

cooling air discharge

 

4)

If Ta 25°C when the heating operation has started or

preventive control by Tc.

 

 

when defrost operation has been cleared, the air

Tc: Indoor heat

 

 

conditioner operates with [L] mode or higher mode for

exchanger sensor

 

 

1 minute after Tc entered in A zone of the cooling air

temperature

 

 

discharge preventive control (Item 7).

 

 

 

 

 

5)

In automatic cooling/heating operation, the mode enters

Display: [AUTO]

 

 

in [AUTO].

 

 

 

 

 

 

 

 

 

 

7 Cool air discharge

1)

In heating operation, the indoor fan is controlled based

In D zone, the priority is

preventive control

 

on the detected temperature of Tc sensor or Tcj sensor.

given to air speed

 

 

As shown below, the upper limit of the revolution

selection setup of

 

 

frequency is restricted.

 

 

 

 

 

remote controller.

 

 

However B zone is assumed as C zone for 6 minutes and

In A and B zones while

 

 

after when the compressor activated.

 

 

 

thermo is ON,

 

 

In defrost operation, the control value of Tc is shifted by

[PRE-HEAT

 

 

(Heating ready)] is

 

 

6°C.

 

 

 

 

 

 

 

 

 

 

 

 

displayed.

 

 

 

 

 

 

 

 

 

Tc

(°C)

 

Tcj

 

 

 

32

 

 

HH

 

 

30

 

 

L

 

 

28

D zone

 

LL

 

26

 

 

OFF

C zone

 

20

B zone

 

16

 

A zone

 

 

– 55 –

Page 55
Image 55
Toshiba RAV-SM1403DT-A, RAV-SM1603DT-A, RAV-SM1603ATZG-E 55, Item, Outline of specifications, Remarks, <Cool>, <Heat>