Toshiba RAV-SM1603ATZ-E, RAV-SM1603DT-A 118, Function selection item No. DN list, Item, Contents

Models: RAV-SM1403DT-A RAV-SM1603ATZ-E RAV-SM1603ATZG-E RAV-SM1603DT-A

1 157
Download 157 pages 61.3 Kb
Page 118
Image 118

Function selection item No. (DN) list

DN

Item

 

 

Contents

At shipment from factory

 

 

 

 

 

 

 

 

0000: None

 

0001: 150H

 

01

Filter sign lighting time

0002: 2500H

 

0003: 5000H

According to type

 

 

0004: 10000H

 

0005: Clogging sensor used

 

 

 

 

 

 

 

03

Central control address

0001: No.1 unit

to

0064: No.64 unit

0099: Undecided

0099: Undecided

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0000: No shift

 

0001: +1°C

0002: +2°C

06

Heating suction temp. shift

0002: +2°C

to

0010: +10°C

(Floor type 0000: 0°C)

 

 

 

 

(Up to +6 is recommended.)

 

 

 

 

 

 

 

 

 

10

Type

0000: (1-way air discharge cassette)

According to model type

0001: (4-way air discharge cassette) to 0037

 

 

 

 

 

 

 

 

 

11

Indoor unit capacity

0000: Undecided

 

0001 to 0034

According to capacity type

 

 

 

 

 

 

12

Line address

0001: No.1 unit

to

0030: No.30 unit

0099: Undecided

 

 

 

 

 

 

13

Indoor unit address

0001: No.1 unit

to

0064: No.64 unit

0099: Undecided

 

 

 

 

 

 

14

Group address

0000: Individual

 

0001: Master unit in group

0099: Undecided

0002: Follower unit in group

 

 

 

 

 

 

 

 

 

 

 

 

In automatic cooling/heating, temp.

0000: 0 deg

to

0010: 10 deg

0003: 3 deg

1E

width of cool heat, heat

(Cool/heat are reversed with ± (Data value) /

(Ts±1.5)

 

cool mode selection control point

2 against the set temperature)

 

 

 

 

 

 

 

 

28

Automatic reset of power failure

0000: None

 

0001: Provided

0000: None

 

 

 

 

 

 

2A

Selection of option / error input (CN70)

0000: Filter input

 

0001: Alarm input

0002: Humidifier

0002: Humidifier input

 

(Air cleaner, etc.)

 

 

 

 

 

 

 

 

 

2b

Selection of thermostat output

0000: Indoor thermostat ON

 

0000: Thermostat ON

(T10 ƒ )

0001: ON receiving output of outdoor compressor

 

 

 

 

 

 

 

 

31

Fan (Single operation)

0000: Impossible

 

0001: Possible

0000: Impossible

 

 

 

 

 

 

32

Sensor selection

0000: Body TA sensor

 

0001: Remote controller sensor

0000: Body sensor

 

 

 

 

 

 

 

 

0000: No control

 

 

 

 

Humidifier control

0001: Humidifier + Vaporizing type (Pump ON)

0003: Humidifier ON

40

(+Drain pump control)

0002: Humidifier + Supersonic type

Pump OFF

 

(This function is not provided.)

(Pump ON when specified time elapsed)

 

 

 

 

0003: Humidifier + Natural drain type (Pump OFF)

 

 

 

 

 

 

 

60

Timer setting (Wired remote controller)

0000: Operable

 

0001: Operation prohibited

0000: Operable

 

 

 

 

 

 

C2

Current demand X% to outdoor unit

0050: 50%

to

0100: 100%

0075: 75%

 

 

 

 

 

 

D0

Existence of remote controller save

0000: Invalid (Impossible)

0001: Valid (Possible)

0001: Valid (Possible)

function

 

 

 

 

 

 

 

 

 

 

 

Restriction ratio setting for save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).