<Formula for Calculating Additional Refrigerant Amount>

Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it is.

Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg)

+ Branch piping additional refrigerant amount (kg) = {α × (L – 28)} + {γ × (a + b + c – 6)}

α: Additional refrigerant amount per meter of actual main piping length (kg)

γ: Additional refrigerant amount per meter of actual branch piping length (kg)

L : Actual length of main piping (m)

a, b, c : Actual length of branch piping (m)

 

Connecting pipe diameter

 

 

 

 

Additional refrigerant amount per Meter (kg/m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

a

 

b

c

 

 

 

α

β

 

 

 

γ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ø 9.5

Ø 6.4

 

Ø 6.4

Ø 6.4

 

0.04

 

 

 

0.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit A

 

Indoor unit C

 

Indoor unit B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Branch pipe

h

Branch pipe

b

Branch pipe

c

a

H

Distributor

L

Main pipe

Outdoor unit

CAUTION

1.Be certain to wire the additional refrigerant amount, pipe length (actual length), head and other specification on the nameplate put on the outdoor unit for recording.

2.Seal the correct amount of additional refrigerant in the system.

– 49 –

Page 49