6-8. Additional Refrigerant Amount

6-8. Additional Refrigerant Amount

nTwin system

<Formula for Calculating Additional Refrigerant Amount>

Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it is.

Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg)

+ Branch piping additional refrigerant amount (kg) = α × (L – 18) + γ × (a + b – 4)

α: Additional refrigerant amount per meter of actual main piping length (kg)

γ: Additional refrigerant amount per meter of actual branch piping length (kg) L : Actual length of main piping (m)

a, b : Actual length of branch piping (m)

Standard piping length

Connecting pipe diameter

Additional refrigerant amount per Meter (kg/m)

 

 

 

 

 

 

 

 

Main piping

Branch piping

L

a

b

α

β

γ

 

 

 

 

 

 

 

 

18 m

2 m

Ø 9.5

Ø 6.4

Ø 6.4

0.040

0.020

 

 

 

 

 

 

 

 

Indoor unit A

Indoor unit B

nTwin systemh

Distributor

b

a

Branch pipe

Branch pipe

L

Main pipe

H

Outdoor unit

CAUTION

1.Be certain to wire the additional refrigerant amount, pipe length (actual length), head and other specification on the nameplate put on the outdoor unit for recording.