nCalling of error history

nCalling of error history

<Contents>

The error contents in the past can be called.

<Procedure>

1

SET

TEST

Push +

buttons simultaneously for
4 seconds or more to call the service check mode.

Service Check goes on, the item code 01 is displayed, and then the content of the latest alarm is displayed. The number and error contents of the indoor unit in which an error occurred are displayed.

2 In order to monitor another error history, push the set

temperature Push + / buttons simultaneously for buttons to change the error history No. (Item code).

Item code ￿￿ (Latest) Item code ￿" (Old)

NOTE : 4 error histories are stored in memory.

3 Pushing TEST button returns the display to usual display.

TEMP.

 

 

ON / OFF

 

 

TIMER SET

FAN

MODE

 

 

TIME

SA

VENT

FIL

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 3 1

<Operation procedure>

1 4 seconds or more to call the service check mode. 2 Item code ￿￿ (Latest) → Item code ￿" (Old) 3

Returned to usual display

REQUIREMENT

CL

Do not push (Group control operation) button, otherwise all the error histories of the indoor unit are deleted.

(Group control operation)

In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.

The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to setting on the remote controller.

<System example>

OUT

 

IN

1-1

 

OUT

IN

Master 2-1

OUT

 

IN

3-1

 

OUT

 

IN

4-1

 

OUT

 

IN

7-1

 

Max. 8 units

Remote controller

1.Display range on remote controller

The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the master unit is reflected on the remote controller.

1)Concealed duct (RAV-SMXXXDT) is not set up on the master unit.

If the Concealed duct is the master unit:

Operation mode: [Cooling/Heating AUTO] [HEAT] [COOL] [FAN] and no [DRY]

Air volume select: [HIGH]

When the operation mode is [DRY], [FAN] stops in duct models.

2.Address setup

Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic address.

If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the system is rebooted and the automatic address setting will be judged again.

1)Connect 3 In/Out cables surely.

2)Check line address/indoor address/group address of the unit one by one.

3)The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the unit No. is not duplicated with one of another unit.

– 121 –

Page 121
Image 121
Toshiba RAV-SM1603ATZG-E Requirement, nCalling of error history, 121, <Contents>, Procedure, Push +, <System example>