nCalling of sensor temperature display

12-1-6. Monitor Function of Remote Controller Switch

nCalling of sensor temperature display

<Contents>

Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller.

<Procedure>

1

TEST

CL

Push
+ buttons simultaneously for 4 seconds to
call the service monitor mode.

The service monitor goes on, the master indoor unit No. is displayed at first and then the temperature of item code ￿￿ is displayed.

2 Push temperature set

ò

 

TEMP.

buttons and then change

 

the item code of data to be monitored.

The item code list is shown below.

TEMP.

 

 

ON / OFF

 

TIMER SET

FAN

MODE

 

TIME

SAVE

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

2 4 1 3

<Operation procedure>

 

Item code

Data name

Unit

 

 

 

 

 

 

 

01

Room temperature

°C

 

 

 

(Remote controller)

 

data

 

02

Indoor suction temperature (TA)

°C

 

03

Indoor heat exchanger (Coil)

°C

unit

 

 

temperature (TCJ)

 

 

04

Indoor heat exchanger (Coil)

°C

Indoor

 

 

 

temperature (TC)

 

07

Indoor fan revolution frequency

rpm

F2

Indoor fan calculated operation time

×100h

 

 

 

F3

Filter sign time

×1h

 

F8

Indoor discharge temperature*1

°C

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Returned to usual display

 

 

 

 

 

 

 

 

 

 

 

Item code

 

Data name

 

 

 

 

 

Unit

 

 

 

 

 

 

 

60

Outdoor heat exchanger (Coil) temperature (TE)

°C

data

 

61

Outside temperature (TO)

 

 

 

 

 

°C

 

62

Compressor discharge temperature (TD)

 

 

°C

 

 

 

 

unit

 

63

Compressor suction temperature (TS)

 

 

°C

 

65

Heat sink temperature (THS)

 

 

 

 

 

°C

Outdoor

 

6A

Operation current (× 1/10)

 

 

 

 

 

A

6D

Outdoor heat exchanger (Coil) temperature (TL)

°C

70

Compressor operation frequency

 

 

rps

 

72

Outdoor fan revolution frequency (Lower)

 

 

rpm

 

73

Outdoor fan revolution frequency (Upper)

 

 

rpm

 

 

F1

Compressor calculated operation time

 

 

×100h

 

 

 

 

 

 

 

 

 

 

 

 

 

Item with marks are not provided to the Concealed Duct Type.

3

ò

Push UNIT LOUVER button to select the indoor unit to be monitored.

 

Each data of the indoor unit and its outdoor units can be monitored.

4

ò

TEST

Pushing button returns the status to the usual display.

1 The indoor discharge temperature of item code [F8] is the estimated value from TC or TCJ sensor.

Use this value to check discharge temperature at test run.

(A discharge temperature sensor is not provided to this model.)

The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.

If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73] are not displayed.

– 120 –

Page 120