Error mode detected by indoor unit

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

Judgment and measures

Check

Cause of operation

Status of

Condition

 

 

 

code

air conditioner

 

 

 

 

 

 

 

 

 

 

 

 

 

No communication from remote

Stop

Displayed when

1.

Check cables of remote controller and communication adapters.

 

 

 

E03

controller (including wireless) and

 

• Remote controller LCD display OFF (Disconnection)

(Automatic reset)

error is detected

 

 

communication adapter

 

 

 

 

 

 

• Central remote controller [97] check code

 

 

 

 

 

 

 

 

 

 

 

 

The serial signal is not output from

 

 

1.

Outdoor unit does not completely operate.

 

outdoor unit to indoor unit.

 

 

 

Inter-unit wire check, correction of miswiring

 

 

 

 

 

 

• Miswiring of inter-unit wire

Stop

Displayed when

 

• Check outdoor P.C. board. Correct wiring of P.C. board.

E04

• Defective serial sending circuit on

 

(Automatic reset)

error is detected

2.

When outdoor unit normally operates

 

outdoor P.C. board

 

 

 

 

 

 

Check P.C. board (Indoor receiving / Outdoor sending).

 

 

 

 

 

 

• Defective serial receiving circuit on

 

 

 

 

 

indoor P.C. board

 

 

 

 

 

 

 

 

 

 

E08

Duplicated indoor unit address

 

 

1.

Check whether remote controller connection (Group/Individual)

 

 

 

 

 

was changed or not after power supply turned on

 

 

 

 

 

L03

Duplicated indoor master unit

 

Displayed when

 

(Finish of group construction/Address check).

 

 

Stop

 

* If group construction and address are not normal when the

 

 

 

 

 

error is detected

 

 

There is group wire in individual indoor

 

power has been turned on, the mode automatically shifts to

L07

 

 

 

 

 

unit.

 

 

 

address setup mode. (Resetting of address)

 

 

 

 

 

 

 

 

 

 

L08

Unset indoor group address

 

 

 

 

 

 

 

 

 

L09

Unset indoor capacity

Stop

Displayed when

1. Set indoor capacity (DN=11)

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

L30

Abnormal input of outside interlock

Stop

Displayed when

1. Check outside devices.

error is detected

2.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Float switch operation

 

 

1.

Trouble of drain pump

 

 

Displayed when

2. Clogging of drain pump

P10

• Float circuit, Disconnection,

Stop

error is detected

3.

Check float switch.

 

 

 

Coming-off, Float switch contact error

 

 

 

 

 

 

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

4-way valve system error

 

 

1.

Check 4-way valve.

 

Stop

Displayed when

2. Check 2-way valve and check valve.

P19

• After heating operation has started,

(Automatic reset)

error is detected

3.

Check indoor heat exchanger (TC/TCJ).

 

indoor heat exchangers temp. is

 

 

 

 

down.

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

Own unit stops while warning is output

Stop

Displayed when

1.

Judge follower unit while master unit is [E03], [L03], [L07] or [L08].

P31

(Follower unit)

2. Check indoor P.C. board.

to other indoor units.

error is detected

 

(Automatic reset)

 

 

 

 

 

 

 

Coming-off, disconnection or short of

Stop

Displayed when

1.

Check indoor heat exchanger temp. sensor (TCJ).

F01

indoor heat exchanger temp. sensor

2. Check indoor P.C. board.

(Automatic reset)

error is detected

 

(TCJ)

 

 

 

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or short of

Stop

Displayed when

1.

Check indoor heat exchanger temp. sensor (TC).

F02

indoor heat exchanger temp. sensor

2. Check indoor P.C. board.

(Automatic reset)

error is detected

 

(TC)

 

 

 

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or short of

Stop

Displayed when

1.

Check indoor heat exchanger temp. sensor (TA).

F10

indoor heat exchanger temp. sensor

2. Check indoor P.C. board.

(Automatic reset)

error is detected

 

(TA)

 

 

 

 

 

 

 

 

 

 

F29

Indoor EEPROM error

Stop

Displayed when

1. Check indoor EEPROM. (including socket insertion)

• EEPROM access error

(Automatic reset)

error is detected

2.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

Communication error between indoor

 

 

1.

Check indoor P.C. board.

E10

MCU

Stop

Displayed when

 

 

• Communication error between fan

(Automatic reset)

error is detected

 

 

 

 

 

 

 

 

 

 

 

driving MCU and main MCU

 

 

 

 

 

 

 

 

 

 

 

Regular communication error between

Stop

Displayed when

1.

Check remote controller wiring.

 

 

 

E18

indoor aster and follower units and

2.

Check indoor power supply wiring.

(Automatic reset)

error is detected

 

between main and sub units

3.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 