[P22 error]

[P22 error]

Are connections of CN300, CN301, CN302 and

CN303 of P.C. board correct?

YES

Correct connection of connector.

Does the fan rotate without trouble

NO

when handling the fan with hands under condition

 

of removing CN300, CN301, CN302

 

and CN303 from P.C. board?

 

 

 

YES

 

 

 

The status that the resistance values

 

between leads below are 12 to 22.

NO

Between

1

(Red lead)

and

2

(White lead)

 

Between

2

(White lead) and

3

(Black lead)

 

Between

3

(Black lead) and

1

(Red lead) of

 

motor winding of connector (CN301, CN303)

 

 

 

YES

 

 

 

 

The status that there is

 

10k to 12kresistance values between

NO

1 (Yellow lead) and

4

(Pink lead)

 

of motor position detection of connector

 

 

(CN300, CN302) is normal.

 

 

 

YES

 

 

 

CN301, CN303

CN300

CN300 : Motor coil winding

CN301 : Motor position detection

CN301, CN303 : Motor coil winding

CN300, CN302 : Motor position detection

Normal fan motor

(Defective CDB P.C. board)

Defective fan motor

NOTE :

However, GND circuit error inside of the motor is rarely detected even if the above check is carried out. When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

 

RAV-SM160AT-E

 

 

Objective P.C. board

CDB P.C. board (MCC-1531)

 

 

Fan motor winding

CN301/CN303

 

 

Motor position detection

CN300/CN302

 

 

Fan motor model

ICF-280-100

 

 

Motor winding resistance

12 to 22

 

 