n Triple system

n Triple system

 

 

Total length (L + a, L +b, L+c)

 

50 m

 

Pipe length

 

 

 

 

Branch pipe length (a, b, c)

 

15 m

 

(one way)

 

 

 

 

 

Refrigerant pipe

Maximum difference between indoor units

 

10 m

 

 

 

(a – b, b – c, c – d)

 

 

 

 

specification

 

 

 

 

 

 

 

Between indoor units ( h)

 

0.5 m

 

 

 

 

Height

 

 

 

 

 

 

Between indoor unit

 

When outdoor unit heigher

(H)

30 m

 

difference

 

 

 

 

 

 

 

 

 

and outdoor unit

 

When outdoor unit lower

(H)

30 m

 

 

 

 

 

 

 

 

 

Number of bent portions

 

 

10 m or less

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit A

Indoor unit C

Indoor unit B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Branch pipe

h

Branch pipe

b

Branch pipe

c

a

H

Distributor

L

Main pipe

Outdoor unit

CAUTION

When planning a layout for Units A, B and C, comply with the following:

1.The lengths after branching (“a” and “b”, “b” and “c”, “a” and “c”) should be equal if feasible.

Install Units A, B and C so that the difference of the branching lengths becomes less than 10m if the lengths cannot be equal due to the branch pipe position.

2.Install Units A, B and C on the same level.

If Units A, B and C cannot be installed on the same level, the difference in level should be limited to 0.5 m or less.

3.Be certain to install Units A and B and C in the same room. Units A, B and C cannot be operated independently each other.

– 47 –

Page 47
Image 47
Toshiba RAV-SM1403DT-A, RAV-SM1603DT-A n Triple system, 47, Indoor unit A, Indoor unit C, Indoor unit B, Outdoor unit