6-6-7. Recovery Method of Refrigerant

6-6-7. Recovery Method of Refrigerant

RAV-SP1404AT(Z)(ZG)-E

Use the refrigerant recovery switch SW801 on the P.C. board of the outdoor unit to recover refriger- ant when the indoor unit or outdoor unit is moved.

Procedure

1.Turn on the power of the air conditioner.

2.Select the FAN mode for indoor unit operation with the remote controller.

3.Set SW804 on the P.C. board of the outdoor unit to all OFF, and then push SW801 for one second or more.

The air conditioner enters the forced cooling mode for up to 10 minutes.

Operation or handling the valve to recover refrigerant during this time period.

4.Upon completion of refrigerant recovery, close the valve and push SW801 for at least one second to stop operation.

5.Turn off the power.

Refrigerant recovery

P.C. board

 

 

switch SW801

 

 

Optional connector

 

 

CN610

 

 

Special operation

 

 

select switch SW804

 

 

 

4

 

 

3

 

Existing pipe switch

ON 1 2

3 4

SW802

 

ON 1 2

 

 

RAV-SM1603AT(Z)(ZG)-E

Use the refrigerant recovery switch SW802 on the P.C. board of the outdoor unit to recover refriger- ant when the indoor unit or outdoor unit is moved.

Procedure

1.Turn on the power of the air conditioner.

2.Select the FAN mode for indoor unit operation with the remote controller.

3.Press the refrigerant recovery switch SW802 on the P.C. board of the outdoor unit to drive the air conditioner into the forced cooling mode for up to 10 minutes.

Open the valve to start refrigerant recovery.

4.Upon completion of refrigerant recovery, close the valve and press SW802 for at least one second to stop operation.

5.Turn off the power.

Outdoor unit P.C. board

SW802 for RAV-SP1404AT(Z)(ZG)-E refrigerant recovery

 

ON

 

 

 

 

 

 

 

 

SW801 for

 

 

 

 

 

 

 

 

 

existing pipes

 

 

 

 

DANGER

Take care for an electric shock because the P.C.board is electrified.

– 45 –