[3] Writing the setting data to EEPROM

[3] Writing the setting data to EEPROM

The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.

Step 1 Push SET , CL and TEST buttons on the remote controller simultaneously for more than 4 seconds.

In the group control operation, the unit No. displayed for the first time is the header unit No.

At this time, the CODE No. (DN) shows “￿￿￿”. Also, the fan of the indoor unit selected starts its operation and the swing operation starts if it has the louvers.

(The unit No. “￿ Step 7<Fig. 1 RBC-AMT32E>￿” is displayed if the auto-address setting mode is interrupted in [2] step 2 a))

UNIT LOUVER

Step 2 Every time when 3 6 5 1 button is pushed, the indoor unit No. in the group control operation are displayed in order.

(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)

Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing. (You cannot perform this operation if “￿ – 114 –Manual background￿” is displayed.)

Step 3 Select the CODE No. (DN) can be selected by pushing the Manual background / Manual background button for the temperature setting.

Set the indoor unit type and capacity.

The factory-set values shall be written to the EEPROM by changing the type and capacity.

1.Set the CODE No. (DN) to “￿￿￿”. (without change)

2.Select the type by pushing Manual background / Manual background buttons for the timer setting.

(For example, 4-way Air Discharge Cassette Type is set to “0001”. Refer to table 2)

3.Push SET button.

(The operation completes if the setting data is displayed.)

4.Change the CODE No. (DN) to “￿￿￿” by pushing Manual background / Manual background buttons for the temperature setting.

5.Select the capacity by pushing Manual background / Manual background buttons for the timer setting. (For example, 80 Type is set to “0012”. Refer to table 3)

6.Push SET button.

(The setting completes if the setting data are displayed.)

7.Return to the normal stop status by pushing TEST button.

(Approx. 1 minute is needed to start operation of the remote controller.)

Step 4 Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2 above again.

Step 5 Change the CODE No. (DN) to “￿￿￿” by pushing Manual background / Manual background buttons for the temperature setting. (this is the setting for the filter sign lighting time.)

Step 6 Check the setting data displayed at this time with the setting data put down in [1].

1.If the setting data is different, modify the setting data by pushing Manual background / Manual background buttons for the timer setting to the data put down in [1].

The operation completes if the setting data is displayed.

2.If the data is the same, proceed to next step.

Step 7

Change the CODE No. (DN) by pushing

/

buttons for the temperature setting.

 

As described above, check the setting data and modify to the data put down in [1].

Step 8

Repeat the steps 6 and 7.

 

 

 

Step 9

After the setting completes, push TEST button to return to the

 

 

normal stop status. (It takes approx. 1 min until the remote control

<Fig. 1 RBC-AMT32E>

 

operation is available again.)

 

 

 

 

 

 

The CODE No. (DN) are ranged from “￿￿￿” to “..￿”.

The CODE No. (DN) is not limited to be serial No.

Even after modifying the data wrongly and pushing SET button, it is possible to return to the data before modification by pushing CL button if the CODE No. (DN) is not changed.

3 6 5 1

4 2