Toshiba RAV-SM1403DT-A, RAV-SM1603DT-A, RAV-SM1603ATZG-E, RAV-SM1603ATZ-E P19 error, F02 error, 103

Models: RAV-SM1403DT-A RAV-SM1603ATZ-E RAV-SM1603ATZG-E RAV-SM1603DT-A

1 157
Download 157 pages 61.3 Kb
Page 103
Image 103
– 103 –

[P19 error]

 

 

 

 

 

 

Is operation of

NO

4-way valve coil

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-way valve normal?

 

conduction?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Is flow of refrigerant

 

 

 

YES

 

 

 

 

 

 

 

 

Is 4-way valve

 

 

 

 

 

 

 

 

 

 

Check 4-way valve

 

 

 

 

 

by electron expansion

 

 

 

 

 

 

 

 

 

 

 

 

coil terminal 200V

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

valve normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is circuit cable normal?

 

 

 

 

 

 

 

 

 

Check and replace

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

Connection of CN01 on CDB

 

 

 

 

 

electron expansion valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and CN13 on IPDU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Both connectors are Red)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

NO

Are characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check and

 

 

 

 

 

of TC sensor resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

value normal?

 

 

 

 

 

 

 

 

correct circuit.

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check CDB P.C. board.

Defect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace TC sensor.

Check indoor P.C. board.

Defect Replace

Check CDB P.C. board.

Defect Replace

In cooling operation, if high pressure is abnormally raised, [P19 error]/[08 error] may be displayed. In this case, remove cause of pressure up and then check again referring to the item [P04 error]/[21 error].

[F02 error]

Is connection of TC sensor connector (Indoor P.C. board CN101) normal?

YES

Are characteristics of

TC sensor resistance value normal?

YES

Check indoor P.C. board.

Defect Replace

NO

NO

Correct connection of connector.

Replace TC sensor.

Refer to 10-2-6. Relational graph of temperature sensor resistance value and temperature Characteristics-2.

– 103 –

Page 103
Image 103
Toshiba RAV-SM1403DT-A, RAV-SM1603DT-A, RAV-SM1603ATZG-E, RAV-SM1603ATZ-E service manual P19 error, F02 error, 103