Setup at shipment

No.

Item

 

 

Outline of specifications

 

 

Remarks

 

 

 

 

 

9

High-temp.

1)

The heating operation is performed as follows based on the

 

 

release control

 

detected temperature of Tc sensor or Tcj sensor.

 

 

 

 

 

 

• When [M] zone is detected, the commanded frequency is

However this control is

 

 

 

decreased from the real operation frequency. After then

ignored in case of the

 

 

 

the commanded frequency changes every 30 seconds

follower unit of the twin.

 

 

 

while operation is performed in [M] zone.

 

 

 

 

 

 

• In [N] zone, the commanded frequency is held.

 

 

 

 

 

 

• When [L] zone is detected, the commanded frequency is

 

 

 

 

returned to the original value by approx. 6Hz every

 

 

 

 

60 seconds.

 

 

 

 

 

 

 

 

 

 

Setup at shipment

Tc (˚C)

M

 

 

 

Tcj

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control temp. (°C)

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

B

 

 

 

 

 

 

 

 

 

56 (54)

52 (52)

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

When the operation has started or when Tc or Tcj < 30°C at

Same status as that

 

 

start of the operation or after operation start, temperature is

when “thermostat-OFF”

 

 

controlled between values in parentheses of A and B.

 

 

(status that the air

 

 

 

 

 

 

 

 

 

 

 

 

conditioner enters in the

 

 

 

 

 

 

 

 

 

 

 

 

room temp. monitor

 

 

 

 

 

 

 

 

 

 

 

 

mode when the

 

 

 

 

 

 

 

 

 

 

 

 

temperature reached

 

 

 

 

 

 

 

 

 

 

 

 

the setup temperature

 

 

 

 

 

 

 

 

 

 

 

 

on the remote controller)

 

 

 

 

 

10

Drain pump

1)

In cooling operation, the drain pump is usually operated.

 

 

control

2)

If the float switch works while drain pump drives, the

Check code [P10]

 

 

 

(Sold separately)

 

compressor stops, the drain pump continues the operation,

 

 

 

 

and a check code is output.

 

 

 

 

 

 

 

3)If the float switch works while drain pump stops, the compressor stops and the drain pump operates. If the float switch keeps operating for approx. 4 minutes, a check code is output.

11 After-heat

When heating operation stops, in some cases, the indoor fan

elimination

operates with (L) for approx. 30 seconds.

12Frequency fixed <In case of wired remote controller>

operation

1)

When pushing [CHK] button for 4 seconds or more, [TEST]

 

(Test run)

 

is displayed on the display screen and the mode enters in

 

 

Test run mode.

 

2)

Push [ON/OFF] button.

 

3)

Using [MODE] button, set the mode to [COOL] or [HEAT].

 

 

• Do not use other mode than [COOL]/[HEAT] mode.

 

 

• During test run operation, the temperature cannot be

 

 

adjusted.

 

 

• An error is detected as usual.

 

 

• A frequency fixed operation is performed.

 

4)

After the test run, push [ON/OFF] button to stop the operation.

 

 

(Display in the display part is same as the procedure in Item 1.)

 

5)

Push [CHK] button to clear the test run mode.

 

 

([TEST] display in the display part disappears and the

 

 

status returns to the normal stop status.)

– 57 –

Page 57
Image 57
Toshiba RAV-SM1603ATZG-E, RAV-SM1603DT-A, RAV-SM1603ATZ-E 57, Item, Outline of specifications, Remarks, Setup at shipment