Toshiba RAV-SM1603DT-A K 2 J, 56, Outline of specifications, Remarks, <Conditions>, Tc n

Models: RAV-SM1403DT-A RAV-SM1603ATZ-E RAV-SM1603ATZG-E RAV-SM1603DT-A

1 157
Download 157 pages 61.3 Kb
Page 56
Image 56
K

No.

Item

Outline of specifications

Remarks

 

 

 

 

8

Freeze preventive control

1) The cooling operation (including Dry operation) is

Tcj:

 

(Low temperature release)

performed as follows based on the detected

Indoor heat exchanger

 

 

temperature of Tc sensor or Tcj sensor.

 

 

sensor temperature

 

 

 

 

 

When [J] zone is detected for 6 minutes

 

 

 

(Following figure), the commanded frequency is

 

 

 

decreased from the real operation frequency.

 

 

 

After then the commanded frequency changes

 

 

 

every 30 seconds while operation is performed in

 

 

 

[J] zone.

 

 

 

In [K] zone, time counting is interrupted and the

 

 

 

operation is held.

 

 

 

When [ I ] zone is detected, the timer is cleared

 

 

 

and the operation returns to the normal operation.

 

 

 

If the commanded frequency becomes S0

 

 

 

because the operation continues in [J] zone, the

 

 

 

return temperature A is raised from 5°C to 12°C

 

 

 

until [ I ] zone is detected and the indoor fan

 

 

 

operates with [L] mode.

 

(˚C)

5

I

A

K

2

J

In heating operation, the freeze-preventive control

Tcn:

works if 4-way valve is not exchanged and the

Tc temperature when 5

following conditions are satisfied.

minutes elapsed after

(However the temperature for J zone dashing

activation

control is changed from 2°C to –5°C.)

 

<Conditions>

Tc (n – 1):

Tc temperature at start

• When Q or R is established 5 minutes after

time

activation.

 

QTcn Tc (n – 1) – 5

 

RTcn < Tc (n – 1) – 1 and Tcn Ta < 5°C

 

– 56 –

Page 56
Image 56
Toshiba RAV-SM1603DT-A, RAV-SM1603ATZG-E, RAV-SM1603ATZ-E K 2 J, 56, Outline of specifications, Remarks, <Conditions>, Tc n