Toshiba RAV-SM1603ATZ-E, RAV-SM1603DT-A service manual 54, Item, Outline of specifications, Remarks

Models: RAV-SM1403DT-A RAV-SM1603ATZ-E RAV-SM1603ATZG-E RAV-SM1603DT-A

1 157
Download 157 pages 61.3 Kb
Page 54
Image 54
– 54 –

No.

Item

 

Outline of specifications

 

 

 

 

Remarks

 

 

 

 

 

 

 

3

Room temp.

1)

Adjustment range: Remote controller setup temperature (°C)

 

control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

 

HEAT

 

 

AUTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired type

 

18 to 29

 

18 to 29

 

18 to 29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless type

 

18 to 30

 

16 to 30

 

17 to 27

 

 

 

 

 

 

 

 

 

 

 

2)

Using the Item code 06, the setup temperature in heating Shift of suction tempera-

 

 

 

operation can be corrected.

 

 

 

 

 

 

ture in heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

 

0

 

2

 

4

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp. correction

 

+0°C

+2°C

 

+4°C

 

+6°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup data

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Automatic

1)

Based on the difference between Ta and Ts, the operation

 

capacity control

 

frequency is instructed to the outdoor unit.

 

 

 

 

(GA control)

2)

Cooling operation

 

 

 

 

 

 

 

 

 

 

 

Every 90 seconds, the room temperature difference between temperature detected by Ta and Ts and the varied room temperature value are calculated to obtain the correction value of the frequency command and then the present frequency command is corrected.

Ta (n) – Ts (n)

: Room temp. difference

n

: Counts of detection

Ta (n-1) – Ts (n)

: Varied room temp. value

n – 1

: Counts of detection of 90 seconds before

3)Heating operation

Every 1 minute (60 sec.), the room temperature differ- ence between temperature detected by Ta and Ts and the varied room temperature value are calculated to obtain the correction value of the frequency command and then the present frequency command is corrected.

 

Ts (n) – Ta (n)

 

 

: Room temp. difference

 

 

n

 

 

: Counts of detection

 

 

Ta (n) – Ta (n – 1) : Varied room temp. value

 

 

n – 1

 

 

: Counts of detection of 1 minute before

 

 

 

 

5 Automatic

1) The judgment of selecting COOL/HEAT is carried out as

 

cooling/

shown below. When +1.5 exceeds against Tsh 10 minutes

Tsc: Setup temp. in

heating control

and after thermo.-OFF, heating operation (Thermo. OFF)

cooling operation

 

exchanges to cooling operation. Description in the

 

Tsh: Setup temp. in

 

parentheses shows an example of cooling ON/OFF.

 

heating operation

 

 

 

 

 

 

 

 

 

Ta

 

Cooling

+ temp. correction of

 

 

room temp. control

 

(˚C)

 

 

 

 

 

 

 

 

 

+1.5

 

 

 

 

 

 

 

 

 

 

 

 

(Cooling ON)

 

 

or Tsc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tsh

 

 

 

 

 

 

 

 

-1.5

 

 

 

(Cooling OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

When –1.5 lowers against Tsc 10 minutes and after thermo. OFF, cooling operation (Thermo. OFF) exchanges to heating operation.

2)For the automatic capacity control after judgment of cooling/heating, see Item 4.

3)For temperature correction of room temp. control in automatic heating, see Item 3.

– 54 –