Toshiba RAV-SM1603ATZ-E, RAV-SM1603DT-A, RAV-SM1603ATZG-E L09 error, L20 error, L30 error, 98

Models: RAV-SM1403DT-A RAV-SM1603ATZ-E RAV-SM1603ATZG-E RAV-SM1603DT-A

1 157
Download 157 pages 61.3 Kb
Page 98
Image 98
– 98 –

[L09 error]

 

Is not yet capacity setting

YES

 

 

 

of indoor unit set up?

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Check indoor P.C. board.

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

[L20 error]

Are wiring connections

NO

to communication lines

 

 

X and Y normal?

 

 

 

YES

 

 

 

 

NO

Is the central controller

 

[98]displayed?

YES

Is the indoor remote controller

[L20] displayed?

 

YES

 

 

 

 

 

 

YES

 

Is not the multiple same central

 

 

 

control system addresses connected?

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Check central controller

 

 

 

(including network adapter).

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

[L30 error]

 

Are outside devices of

NO

 

 

 

connector CN80 connected?

 

 

 

 

 

 

YES

 

 

 

 

 

 

NO

 

Do outside devices normally work?

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Check cause of operation.

 

 

 

 

 

 

 

 

 

 

 

 

Set capacity data of indoor unit.

(Setup item code (DN)=11)

Correct wiring connection.

Check indoor P.C. board.

Defect Replace

Correct central control system address.

Check indoor P.C. board.

Defect Replace

Check outside devices.

Defect Replace

– 98 –