Briggs & Stratton 206484GS manual Final Installation Considerations, Initial Start-up No Load

Page 17

Final Installation Considerations

Engine Oil

notice

Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.

Refer to Maintenance and engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.

This engine is shipped from the factory pre-run and filled with synthetic oil (API SJ/CF 5W-30W). This allows for system operation in the widest range of temperature and climate conditions. Before starting the engine, check oil level and ensure that engine is serviced as described in the engine operator’s manual.

NOTE: The use of synthetic oil does not alter the required oil change intervals described in the engine operator’s manual.

Battery

The home generator is supplied with a sealed, lead-acid, rechargeable, 12 Volt DC 33 Amp-Hour, 350 cold cranking amps (CCA), valve regulated battery. It is installed in the unit and the battery cables are connected at the factory.

With the battery installed, all wiring to transfer switch and home generator completed, utility power supplied to the Automatic Transfer Switch, and the system switch in the AUTO position, the battery receives a trickle charge while the engine is not running. The trickle charge cannot be used to recharge a battery that is completely discharged.

15 Amp Fuse

The generator’s 15 Amp fuse was removed at the factory to prevent the unit from starting during shipping. Your installer will ensure the fuse is properly installed upon completion of the installation.

Fuel Supply System

Ensure that all fuel pipe connections are tight, secure and without leaks.

Ensure that all gas line shutoff valves are OPEN and that adequate fuel pressure is available whenever automatic operation is desired.

Fuel System Selection

The engine of your Home Generator System is factory calibrated to run on natural gas (NG). It may also be operated on liquid propane (LP) vapor.

To configure the fuel system for LP use:

1.LP fuel inlet pressure must be between 11 and 14 inches water column.

2.Set AUTO/OFF switch to OFF.

3.Turn OFF the main distribution panel circuit breaker sending power to the automatic transfer switch.

4.Remove 15 Amp fuse.

5.Change main jet in fuel mixer following instruction sheet provided in LP conversion kit.

6.Reinstall 15 Amp fuse.

7.Turn ON the main distribution panel circuit breaker that supplies utility power to the automatic transfer switch.

8.Set AUTO/OFF switch to AUTO.

9.Reset exercise timer following instructions Setting Exercise Timer.

The generator is now ready to operate automatically using LP fuel. With a fixed main jet for LP gas, there is no need to perform any engine adjustments for LP operation.

Initial Start-up (No Load)

Before operating the home generator or placing it into service, inspect the entire installation carefully.

Then begin testing the system without any electrical loads connected, as follows:

1.Set generator’s main circuit breaker to its ON (closed) position.

2.Install 15 Amp fuse in control panel.

3.Set generator’s system switch to AUTO.

4.Push MANUAL OVER-RIDEbutton on control panel.

NOTE: When the home generator is started for the very first time, it will require that air in the gaseous fuel lines be purged. This may take a few minutes.

5.DO NOT crank engine for more than 10 seconds, then pause for 10 seconds to reduce heat in the starter.

6.Repeat process until engine starts.

7.Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks while engine runs.

8.Let engine warm up for about five minutes to allow internal temperatures to stabilize.

9.Connect an RMS AC voltmeter and a frequency meter to check generator output at load side of circuit breaker. Voltage should be 230‑240 Volts, frequency should be 62.0 - 62.5 Hz.

10.Check generator output between one of the generator connection lugs and the neutral lug, then between the other generator connection lug and the neutral lug.

In both cases, voltage reading should be between 115‑120 Volts.

11.Push and hold MANUAL OVER-RIDEbutton on control panel again until engine stops.

Installation Inspection

Complete the ”Installation Checklist” as you make the inspection. Ensure all items have been filled-in and all signatures have been obtained. Instruct the owner to mail the white copy to:

Briggs & Stratton Power Products Warranty Registration

P. O. Box 239

Jefferson, WI 53549-0239

17

Image 17
Contents Watt Home Generator System Date of Purchase Generator Where to Find UsEngine Model Number Model Revision Serial NumberTable of Contents BRIGGSandSTRATTON.COM Safety RulesHazard Symbols and Meanings Page See Essential Circuits Owner Orientation InstallationLifting the Generator Fuel FactorsGeneral Location Guidelines Home Generator LocationGenerator Location Essential Circuits To Remove Access Cover Access CoversTo Install Access Cover and Roof Fuel and Electrical Inlet LocationsManometer port should be provided BRIGGSandSTRATTON.COM Gaseous Fuel SystemFuel Consumption Natural Gas LP VaporFuel Pipe Sizing 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ftLP Vapor Natural Fuel Comparison ChartGas Required Propane Tank Size+12 Volt DC, .5 Amp Output Internal auxiliary power supply System ConnectorsPole Connector Plug Fault Detection System Transfer Switch CommunicationTo install the remote LED indicator Generator AC Connection SystemInitial Start-up No Load Final Installation ConsiderationsUnit Identification Label Identifies unit by serial number Features and ControlsHome Generator System Control Panel Automatic Operation OperationAutomatic Operation Sequence Setting Exercise Timer Servicing the System MaintenanceFault Detection System Transfer Switch Fault High TemperatureLow Voltage Generator Engine Fail To StartGenerator Maintenance Servicing the Battery BatteryCharging the Battery Storage To Clean the GeneratorWhen Calling the Factory Problem Cause Correction TroubleshootingDown when loads are connected AvailableSchematic Wiring Diagram Limited Warranty Page Common Service Parts Product SpecificationsAt 120 Volts At 240 VoltsWatt Fecha de compra Generador Dónde encontrarnosMotor Número de Modelo Revisión Número de SerieReglas de seguridad Problemas Garantía Especificaciones del productoInstalación Controles y característicasSímbolos de Peligro y Significados Reglas de seguridadAte para arriba el pelo largo y quite la joyería Tensión peligrosaNo modifique al generador en ninguna forma Instala el fusible se puede producir el arranque del motorOrientación para el propietario InstalaciónInspección al Momento de la Entrega Factores Relacionados con el CombustiblePrecauciones al Momento del Desempaque Ubicación del Sistema de Generador de Doméstico Elevación del GeneradorUbicación del Generador Pautas Generales para la Ubicación del GeneradorSelección de los Circuitos Fundamentales Circuitos FundamentalesDispositivo Vatiaje de Sistema de combustible gaseoso Dimensiones de la Entrada para Electricidad y CombustiblePuertas de Acceso Se debe contar también con una abertura para manómetro Vapor de Gas Gas Natural Vapor de PLCableado para toma de 10 polos Conexiones de SistemaCableado para toma bipolar Conexión a Tierra del Generador Sistema de Conexión de c.a. del GeneradorInterconexiones del Circuito de Control Comunicación del conectadorConsideraciones finales para la instalación Inspección posterior a la instalación Arranque inicial sin cargaInstale el fusible de 15 Amperios en el panel de control Generador Doméstico Controles y característicasAjustes. Conserve este manual para referencias futuras Calcomanía de Datos de la Unidad Identifica a laPanel de control del sistema Secuencia de operación automática UtilizaciónFuncionamiento Automático Temporizador de enfriamiento del motorConfiguración del temporizador de práctica Sistema de Detección de Fallas MantenimientoParo del Sistema El Motor no Arranca Baja TensiónBaja Frecuencia Sobrevelocidad del MotorMantenimiento del Generador Servicio la Batería BateríaCargar la Batería Si Llama a la Fábrica AlmacenamientoPara Limpiar el Generador Problemas Causa Corrección ProblemasGarantía Limitada Servicio común despide Especificaciones del productoWatt Groupe électrogène Date d’achat Génératrice Où nous trouverMoteur Numéro de modèle Révision Numéro de sérieRègles de sécurité Fonctions et commandesFonctionnement EntreitenRègles de sécurité Symboles de Danger et MoyensSécurité Certains composants de ce produit ainsi que lesTension dangereuse Avis Conseils au propriétaire Responsabilités de l’installateurConservez ces instructions Responsabilités de l’acheteurVérification de la livraison Facteurs relatifs au combustiblePrécautions lors du déballage Directives générales concernant l’emplacement Emplacement du génératrice d’état d’attenteInstallez l’unité à l’extérieur Seulement Soulèvement de la génératrice’illustration suivante montre les dégagements Minimum Circuits essentiels10 Sélection des circuits essentielsSécheuse électrique 750 Sécheuse gaz Scie circulaire 6,5 po 16,5 cmDéshumidificateur Couverture électriquePortes d’accès Pour installer la porte d’accès et le toitLe système de combustible gazeux Pour enlever le toitIl faudrait inclure une sortie pour manomètre Aucune fuite ne peut être toléréePropane Gaz Gas Naturel Vapeur PLConnexions de système Sécurité Système de Branchement C.A. de la Génératrice Interconnexions du Circuit de CommandeNiveau de la génératrice Mise à la Masse de la GénératriceConsidérations pour l’installation finale Démarrage initial sans charge Vérification installationEntretien Dépannage Garantie Fonctions et commandesSécurité Instalación Commandes Fonctionnement Sécurité Instalación Commandes Tableau de commande de systèmeFonctionnement automatique FonctionnementSéquence de fonctionnement automatique Arrêt du Système EntreitenSystème de Détection des Pannes Code de Nombre deFaible Tension de la Batterie Aucun DEL Batterie déchargéeFaible Pression d’Huile Basse TensionEntretien du Générateur Changement du filtre à huile BatteriePour mettre de l’huile dans le moteur Filtre à airEntretien de la Batterie RemisagePour Nettoyer le Générateur 26Dépannage Problème Cause SolutionGarantie Limitée Page Pièces d’entretien courant Caractéristiques du produit