Home Generator Location

Before installing generator, consult with homeowner and convey the following guidelines which may affect the desired location.

WARNING

Exhaust heat / gasses can ignite combustibles or structures causing a fire.

DO NOT install the generator closer than 5 feet (1.5m) from any combustibles or structures with combustible walls having a fire resistance rating of less than 1 hour.

Keep at least minimum distances shown in General Location Guidelines to insure for proper generator cooling and maintenance clearances.

Generator Location

Install generator outdoors in an area which will not accumulate deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area. Prevailing winds and air currents should be taken into consideration when positioning generator.

WARNING

Running engine gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause headache, fatigue, dizziness, vomiting, confusion, seizures, nausea, fainting, or death.

Operate generator ONLY outdoors.

Install a battery operated carbon monoxide alarm near the bedrooms.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes, or other openings.

General Location Guidelines

Install the unit outdoors ONLY.

Place the unit in a prepared location that is flat and has provisions for water drainage.

Install the unit in a location where sump pump discharge, rain gutter down spouts, roof run-off, landscape irrigation, or water sprinklers will not flood the unit or spray the enclosure and enter any air inlet our outlet openings.

Install the unit where the location of any services such as phone, electrical, fuel, air conditioning, irrigation, including covered, concealed and underground services will not be affected or obstructed.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the Transfer Switch and fuel supply to reduce the length of wiring, conduit, and piping.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

The Minimum (MIN) clearances from aerial view of generator (B) to combustible (D), and non-combustible (A) materials is shown below.

These distances are provided to give generator location guidance relative ONLY to combustibles, generator cooling, and maintenance.

The minimum distances in the figure are as shown. All four sides of the generator cannot be enclosed or restricted, even if the minimum distances are maintained. DO NOT connect (A) and/or (D) to (E)

A roof cannot be used.

Exhaust (C) must not be allowed to accumulate.

 

 

5’ (1.5m)

 

 

3’

 

 

(1m)

 

 

3’

 

 

(1m)

 

 

B

 

5’ (1.5m)

5’ (1.5m)

D

A

C

5’ (1.5m)

EE

ANon-Combustible material with Fire Resistant Rating of 1 hour or greater

BHome Generator System

CEngine Exhaust

DCombustible Material or Structure with a Fire Resistance Rating of less than 1 hour.

EAny structure or material. DO NOT connect (A) and/or (D) to (E).

The home generator is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

Image 9
Contents Watt Home Generator System Date of Purchase Generator Where to Find UsEngine Model Number Model Revision Serial NumberTable of Contents Safety Rules Hazard Symbols and MeaningsBRIGGSandSTRATTON.COM Page See Essential Circuits Owner Orientation InstallationLifting the Generator Fuel FactorsHome Generator Location Generator LocationGeneral Location Guidelines Essential Circuits To Remove Access Cover Access CoversTo Install Access Cover and Roof Fuel and Electrical Inlet LocationsManometer port should be provided BRIGGSandSTRATTON.COM Gaseous Fuel SystemFuel Consumption Natural Gas LP VaporFuel Pipe Sizing 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ftLP Vapor Natural Fuel Comparison ChartGas Required Propane Tank SizeSystem Connectors Pole Connector Plug+12 Volt DC, .5 Amp Output Internal auxiliary power supply Fault Detection System Transfer Switch CommunicationTo install the remote LED indicator Generator AC Connection SystemInitial Start-up No Load Final Installation ConsiderationsFeatures and Controls Home GeneratorUnit Identification Label Identifies unit by serial number System Control Panel Operation Automatic Operation SequenceAutomatic Operation Setting Exercise Timer Maintenance Fault Detection SystemServicing the System Transfer Switch Fault High TemperatureLow Voltage Generator Engine Fail To StartGenerator Maintenance Battery Charging the BatteryServicing the Battery To Clean the Generator When Calling the FactoryStorage Problem Cause Correction TroubleshootingDown when loads are connected AvailableSchematic Wiring Diagram Limited Warranty Page Common Service Parts Product SpecificationsAt 120 Volts At 240 VoltsWatt Fecha de compra Generador Dónde encontrarnosMotor Número de Modelo Revisión Número de SerieReglas de seguridad Problemas Garantía Especificaciones del productoInstalación Controles y característicasSímbolos de Peligro y Significados Reglas de seguridadAte para arriba el pelo largo y quite la joyería Tensión peligrosaNo modifique al generador en ninguna forma Instala el fusible se puede producir el arranque del motorOrientación para el propietario InstalaciónFactores Relacionados con el Combustible Precauciones al Momento del DesempaqueInspección al Momento de la Entrega Ubicación del Sistema de Generador de Doméstico Elevación del GeneradorUbicación del Generador Pautas Generales para la Ubicación del GeneradorSelección de los Circuitos Fundamentales Circuitos FundamentalesDispositivo Vatiaje de Dimensiones de la Entrada para Electricidad y Combustible Puertas de AccesoSistema de combustible gaseoso Se debe contar también con una abertura para manómetro Vapor de Gas Gas Natural Vapor de PLConexiones de Sistema Cableado para toma bipolarCableado para toma de 10 polos Conexión a Tierra del Generador Sistema de Conexión de c.a. del GeneradorInterconexiones del Circuito de Control Comunicación del conectadorConsideraciones finales para la instalación Arranque inicial sin carga Instale el fusible de 15 Amperios en el panel de controlInspección posterior a la instalación Generador Doméstico Controles y característicasAjustes. Conserve este manual para referencias futuras Calcomanía de Datos de la Unidad Identifica a laPanel de control del sistema Secuencia de operación automática UtilizaciónFuncionamiento Automático Temporizador de enfriamiento del motorConfiguración del temporizador de práctica Mantenimiento Paro del SistemaSistema de Detección de Fallas El Motor no Arranca Baja TensiónBaja Frecuencia Sobrevelocidad del MotorMantenimiento del Generador Batería Cargar la BateríaServicio la Batería Almacenamiento Para Limpiar el GeneradorSi Llama a la Fábrica Problemas Causa Corrección ProblemasGarantía Limitada Servicio común despide Especificaciones del productoWatt Groupe électrogène Date d’achat Génératrice Où nous trouverMoteur Numéro de modèle Révision Numéro de sérieRègles de sécurité Fonctions et commandesFonctionnement EntreitenRègles de sécurité Symboles de Danger et MoyensSécurité Certains composants de ce produit ainsi que lesTension dangereuse Avis Conseils au propriétaire Responsabilités de l’installateurConservez ces instructions Responsabilités de l’acheteurFacteurs relatifs au combustible Précautions lors du déballageVérification de la livraison Directives générales concernant l’emplacement Emplacement du génératrice d’état d’attenteInstallez l’unité à l’extérieur Seulement Soulèvement de la génératrice’illustration suivante montre les dégagements Minimum Circuits essentiels10 Sélection des circuits essentielsSécheuse électrique 750 Sécheuse gaz Scie circulaire 6,5 po 16,5 cmDéshumidificateur Couverture électriquePortes d’accès Pour installer la porte d’accès et le toitLe système de combustible gazeux Pour enlever le toitIl faudrait inclure une sortie pour manomètre Aucune fuite ne peut être toléréePropane Gaz Gas Naturel Vapeur PLConnexions de système Sécurité Système de Branchement C.A. de la Génératrice Interconnexions du Circuit de CommandeNiveau de la génératrice Mise à la Masse de la GénératriceConsidérations pour l’installation finale Démarrage initial sans charge Vérification installationFonctions et commandes Sécurité Instalación Commandes FonctionnementEntretien Dépannage Garantie Sécurité Instalación Commandes Tableau de commande de systèmeFonctionnement Séquence de fonctionnement automatiqueFonctionnement automatique Arrêt du Système EntreitenSystème de Détection des Pannes Code de Nombre deFaible Tension de la Batterie Aucun DEL Batterie déchargéeFaible Pression d’Huile Basse TensionEntretien du Générateur Changement du filtre à huile BatteriePour mettre de l’huile dans le moteur Filtre à airEntretien de la Batterie RemisagePour Nettoyer le Générateur 26Dépannage Problème Cause SolutionGarantie Limitée Page Pièces d’entretien courant Caractéristiques du produit