Low Voltage (Generator)
This fault is indicated by fault code FC_3 and three blinks on the LED indicator. This condition is caused by a restriction in the fuel flow, a broken or disconnected signal lead, a failed alternator winding, the control panel circuit breaker is open, or the generator is overloaded.
To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
Engine Fail To Start
This fault is indicated by fault code FC_4 and four blinks on the LED indicator. This feature prevents the generator from damaging itself if it continually attempts to start in spite of another problem, such as no fuel supply. Each time the system is directed to start, the unit will crank for 10 seconds, pause for 10 seconds, and repeat. If the system does not begin producing electricity after approximately 2 minutes, the unit will stop cranking and the LED will blink.
Check to make sure the generator’s main circuit breaker is in the ON position in order for the sensing leads to verify that the unit is running.
The most likely cause of this problem is no fuel supply. Check the inside and outside fuel shut off valves to ensure they are fully open. Other causes could be failed spark plug(s), failed engine ignition, or the engine air filter
is clogged. You may need to contact your installer for assistance if you can’t remedy these problems.
Low Frequency
This fault is indicated by fault code FC_5 and five blinks on the LED indicator. This feature protects devices connected to the transfer switch by shutting the generator down
if the engine runs slower than 55 Hz for three seconds. This condition is caused by a failed engine governor or by excessive loads on the generator. To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
Engine Overspeed
This fault is indicated by fault code FC_6 and six blinks on the LED indicator. This feature protects devices connected to the transfer switch by shutting the generator down if the engine happens to run faster than the preset limit. The overspeed fault is detected as follows:
•If the generator output frequency is
•If the generator output frequency is greater than 70 Hz, the generator will shut down immediately.
This condition is caused by a failed engine governor. To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.
High Temperature
This fault is indicated by fault code FC_7 and seven blinks on the LED indicator. The contacts of the temperature switch (A) are normally open. If the engine oil temperature exceeds approximately 148.9°C (300°F), the fault is detected and the engine shuts down.
A
Common causes for this condition include running the unit with all access covers removed, obstructed air inlet or exhaust port, low oil level, or debris in the engine cylinder cooling fins.
To resolve the problem, let the engine cool down and remove any accumulated debris and obstructions. Ensure that the access covers are installed whenever the unit is running.
Transfer Switch Fault
This fault is indicated by fault code FC_8 and eight blinks on the LED indicator (if transfer switch is equipped with fault detection). The most likely cause of this fault is a blown fuse in the transfer switch.
To remedy the problem, contact your installer or a Briggs & Stratton Authorized Dealer.