Carrier JK034-074, 50FK, 48FK specifications Space Temperature Sensor Averaging

Page 18

 

 

 

 

RED

RED

 

 

 

 

BLK

BLK

SIZES 034-048

 

 

 

 

TB3

RED

 

 

RED

RED

12

 

 

 

 

 

 

BLK

15

BLK

 

 

BLK

 

 

 

 

 

TO ACCESSORY SPACE

 

 

 

 

TEMPERATURE RESET

 

 

 

 

CONTROL BOARD

 

 

 

 

SIZES 054-104

 

 

 

 

TB4

 

 

 

 

 

12

 

 

 

 

 

15

 

SENSOR 1

SENSOR 2

SENSOR 3

 

 

 

 

SPACE TEMPERATURE RESET Ð 4 SENSOR AVERAGING APPLICATION

SIZES 034-048

 

 

 

 

TB3

RED

 

 

RED

RED

12

 

 

BLK

 

 

BLK

BLK

15

 

 

 

 

 

 

 

TO ACCESSORY SPACE

 

 

 

 

TEMPERATURE RESET

 

 

 

 

CONTROL BOARD

 

 

SENSOR 1

SENSOR 2

SIZES 054-104

 

BLK

RED

 

 

 

 

 

TB4

 

 

 

 

 

12

 

 

 

RED

RED

15

 

 

 

 

 

 

BLK

BLK

 

 

 

 

 

 

 

BLK

SENSOR 4

SENSOR 5

NOTE: Sensor part number is HH79NZ014.

RED

 

 

 

 

 

 

 

 

RED

RED

 

 

 

 

BLK

BLK

 

 

 

 

SENSOR 7

SENSOR 8

SPACE TEMPERATURE RESET Ð 9 SENSOR AVERAGING APPLICATION

Fig. 26 Ð Space Temperature Sensor Averaging

SENSOR 4

SENSOR 3

SENSOR 6

SENSOR 9

Demand Limit Ð The demand limit function provides a means to limit the cooling capacity of the VAV unit using an external discrete switch function. When enabled by the closure of the external switch, the control will limit the avail- able compressor staging capacity according to user set points established at demand limit potentiometer(s).

The unit controls support two types of demand limit: single- step and 2-step control.

SINGLE-STEP DEMAND LIMIT Ð This function will limit the total compressor staging based on the ratio of the set point potentiometer's wiper arm position to the full scale resis- tance of the potentiometer. The exact percentage of capacity reduction differs depending on the number of capacity steps.

A ®eld-supplied potentiometer and control switch are re- quired for this function. See installation section for speci- ®cation on potentiometer and ®eld wiring.

TWO-STEP DEMAND LIMIT Ð Two-step demand limit is provided with the installation of the accessory Demand Limit

Control Module kit plus installation of 2 ®eld-supplied con- trol switches (SPST-NO each). This accessory control pro- vides for a ®rst step reduction of 50% to 100% of the maxi- mum compressor staging; the second step provides for reduction between 0% and 49%. The exact percentage of capacity re- duction differs depending on the number of capacity steps.

When demand limit is active, the LED display will show

code 22 .

INSTALLATION

Single-Step Demand Limit Ð A 3-wire 5 to 20 K-ohm po- tentiometer must be ®eld-supplied and installed. A single- pole normally open switch is also required (®eld-supplied and -installed). Locate the potentiometer (designated P4) and the switch in a suitable location (external from the unit or in the unit control box).

18

Image 18
Contents Controls Operation Troubleshooting ContentsSafety Considerations GeneralDIP Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input EXV034-104 Status Switch InputsConnector J2 Status Switch Unit Size Terminal no RNT Ð ReturnPage HIR Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Integrated Circuit InputControls Installation Space Temperature ResetUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Voltage Drop Characteristics Thermistor ResistanceSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Switches Required for Each Mode Smoke Control ModesSwitch Functions Tubing SizeDPS Ð Differential Pressure Switch SwitchTerminal Block Modulating Power Exhaust Differential Pressure Switch Sizes START-UPConguration Header DIP Switch Factory Settings Potentiometer Inputs and RangesConguration Header Jumpers DIP Switches Switch Function Meaning PositionInlet Guide Vane Motor 50FK,JK034-074 Units Jumper Removal to Disable Motor Variable Frequency Drive KeypadControl Signal Pressure VFD SET Point VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command PressureStart Unit Quick Test, Unit Conguration and Switch Check Quick Normal Description Control Switch Test Display Step noQuick Normal Description Thermistor or Test Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Test Description Relay NumberOperating Information Sensor Resistance ValuesPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 088 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 104 UnitsSymptoms Probable Causes Solutions TroubleshootingControls Troubleshooting Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP4 Terminals Voltage ACTest PIN Voltage DC TP3 TP6Quick Test J9 PIN Numbers Step no PIN Terminal Voltage DCTerminal Strip J6 Connection Resistance Reading Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages PIN Voltage TerminalTerminal Strip J5 Connector Resistance Reading Enthalpy Sensor CheckoutQuick Test J5 PIN Numbers Step no Variable Frequency Drive Carrier Default Program Parameter Values Parameter Group Default ValueRequired User Adjusted Defaults Motor Overload SettingsLPS ALMLAT MTRPage Page Service Training Call for Free CatalogII. Preliminary Checklist Items PRE-START-UPIII. START-UP IV. Notes