Carrier 50FK, JK034-074 Start-Up, Modulating Power Exhaust Differential Pressure Switch Sizes

Page 25

Fig. 33 Ð Modulating Power Exhaust and Inlet

Guide Vane Differential Pressure Switch

(Sizes 034-048)

Fig. 34 Ð Inlet Guide Vane Differential

Pressure Switch and Variable Frequency Drive

Duct Pressure Transducer (Sizes 054-104)

Fig. 35 Ð Modulating Power Exhaust Differential

Pressure Switch (Sizes 054-104)

MODULATING POWER EXHAUST Ð The tubing for the building pressure control (achieved via the Modulating Power Exhaust option) should sample building pressure in the area near the entrance lobby (or other appropriate and sensitive location) so that location is controlled as closely to design pressures as possible.

A differential pressure switch (DPS) is used to control the actuator on the modulating discharge damper in exhaust fan no. 1. The building pressure (BP) DPS is located in the aux- iliary control box of the unit. See Fig. 33 and 35. Use a nomi- nal 3¤8-in. plastic tubing.

For instructions on adjusting BP control set points, refer to Start-Up, Modulating Power Exhaust section in this book.

START-UP

Initial Check

IMPORTANT: Do not attempt to start unit, even mo- mentarily, until all items on the Controls Start-Up Check- list (in installation instructions) and the following steps have been completed.

1.Verify unit has been installed per the Installation Instruc- tions included in the unit installation packet.

2.Verify that all auxiliary components (sensors, controls, etc.) have been installed and wired to the unit control boxes per these instructions, the unit Installation Instructions, and the unit wiring label diagrams.

3.Verify that air pressure hoses (static, duct, etc.) are prop- erly attached, routed, and free from pinches or crimps that may affect proper control operation.

4.Set any control con®gurations that are required (®eld- installed accessories, etc.). The unit is factory con®gured for all appropriate factory-installed options with the ap- plicable controls programmed to the default values.

5.Check and adjust unit set points. See Table 9.

6.Check tightness of all electrical connections.

7.Perform quick test (see Quick Test Program section on page 31).

25

Image 25
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsConnector J1 Temperature Unit Size Terminal no Input Pin Terminal Connector J1 Thermistor InputsDIP EXVConnector J2 Status Switch Unit Size Terminal no Status Switch Inputs034-104 RNT Ð ReturnPage Output PIN Name Rating Device Terminal Output Pin and Terminal AssignmentsHIR IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsSwitch DPS Ð Differential Pressure SwitchTerminal Block START-UP Modulating Power Exhaust Differential Pressure Switch SizesPotentiometer Inputs and Ranges Conguration Header DIP Switch Factory SettingsConguration Header Jumpers Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorChanging the VFD Set Point Frequency Command VFD Set Point Frequency Command for Duct PressureControl Signal Pressure VFD SET Point PressureStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Test, Output Relay Check Quick Test, Thermistor and Potentiometer CheckQuick Normal Description Thermistor or Test Quick Normal Test Description Relay NumberSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 064 Units Cooling Size 054 UnitsCooling Size 088 Units Cooling Size 104 UnitsControls Troubleshooting TroubleshootingSymptoms Probable Causes Solutions Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page Test PIN Voltage DC TP3 Terminals Voltage ACTP4 TP6PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPin Terminal Connector J2 Voltages Pin Terminal Connector J1 VoltagesTerminal Strip J6 Connection Resistance Reading PIN Voltage TerminalEnthalpy Sensor Checkout Terminal Strip J5 Connector Resistance ReadingQuick Test J5 PIN Numbers Step no Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsLAT ALMLPS MTRPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP