Table 7 Ð Switch Functions
| SWITCH |
| CONFIGURATION | VOLTAGE | FUNCTION | ||
| NUMBER |
| |||||
|
|
|
|
|
| ||
|
|
| N.C. | 115 | Deenergize | ||
|
|
| N.C. | 115 | Deenergize TRAN7 (Process Board) | ||
|
|
| N.O. | 24 | Energize EOR (Open Economizer Outside Air Dampers) | ||
|
|
| N.O. | 115 | Energize IFC and | ||
|
|
| N.C. | 115 | Isolate IFC and PEC for Separate Operation | ||
|
|
| N.O. | 115 | Energize PEC (Power Exhaust) | ||
|
|
| N.O. | 24 | Open PED at DPS | ||
|
|
| N.C. | 24 | Block | ||
|
|
| A: N.O. | 115 max | Signal Room Terminals to Open (HIR1) | ||
|
|
| B: N.C. | ||||
|
|
|
|
|
|
| |
|
| LEGEND |
|
|
|
| |
BP | Ð Building Pressure |
|
|
|
| ||
DPS | Ð Differential Pressure Switch |
|
| ||||
EOR Ð Economizer Open Relay |
|
| |||||
HIR | Ð | Heat Interlock Relay |
|
|
| ||
IFC | Ð | Indoor Fan Contactor |
|
|
| ||
IGV | Ð | Inlet Guide Vane |
|
|
|
| |
N.C. | Ð | Normally Closed |
|
|
|
| |
N.O. | Ð | Normally Open |
|
|
|
| |
PEC | Ð Power Exhaust Contactor |
|
| ||||
PED | Ð Power Exhaust Damper |
|
| ||||
OFC | Ð Outdoor Fan Contactor |
|
|
| |||
VFD | Ð Variable Frequency Drive |
|
|
Air Pressure Tubing Ð Before options such as inlet guide vanes (IGV), variable frequency drive (VFD), and/or modulating power exhaust can operate properly, the pneu- matic tubing for pressure sensing must be installed. Use ®re- retardent plenum tubing
Table 8 Ð Tubing Size
OPTION | UNITS | NOMINAL TUBE | |
SIZE (in.) | |||
|
| ||
Inlet Guide Vanes (IGV) | ALL | 3¤8 | |
Variable Frequency | ALL | 1¤4 | |
Drive (VFD) | |||
|
| ||
Modulating Power Exhaust | FK,FKX,JK,JKX | 3¤8 |
INLET GUIDE VANES Ð The tubing for the duct pressure (DP) control option should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.
The inlet guide vanes are controlled by a differential pres- sure switch (DPS). On sizes
VARIABLE FREQUENCY DRIVE Ð The tubing for the duct pressure (DP) control option should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.
The duct pressure is sensed by a pressure transducer. The pressure transducer output is directed to the VFD. On 034- 048 units the DP transducer is located in the auxiliary con- trol box. On
23