Carrier 48FK, JK034-074, 50FK specifications Switch Functions, Tubing Size

Page 23

Table 7 Ð Switch Functions

 

SWITCH

 

CONFIGURATION

VOLTAGE

FUNCTION

 

NUMBER

 

 

 

 

 

 

 

 

SW-1

 

 

N.C.

115

Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)

 

SW-2

 

 

N.C.

115

Deenergize TRAN7 (Process Board)

 

SW-3

 

 

N.O.

24

Energize EOR (Open Economizer Outside Air Dampers)

 

SW-4

 

 

N.O.

115

Energize IFC and CR-3 (IGV/VFD)

 

SW-5

 

 

N.C.

115

Isolate IFC and PEC for Separate Operation

 

SW-6

 

 

N.O.

115

Energize PEC (Power Exhaust)

 

SW-7

 

 

N.O.

24

Open PED at DPS

 

SW-8

 

 

N.C.

24

Block Auto-Close at DPS (Due to Low BP)

 

SW-9A/B

 

 

A: N.O.

115 max

Signal Room Terminals to Open (HIR1)

 

 

 

B: N.C.

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

BP

Ð Building Pressure

 

 

 

 

DPS

Ð Differential Pressure Switch

 

 

EOR Ð Economizer Open Relay

 

 

HIR

Ð

Heat Interlock Relay

 

 

 

IFC

Ð

Indoor Fan Contactor

 

 

 

IGV

Ð

Inlet Guide Vane

 

 

 

 

N.C.

Ð

Normally Closed

 

 

 

 

N.O.

Ð

Normally Open

 

 

 

 

PEC

Ð Power Exhaust Contactor

 

 

PED

Ð Power Exhaust Damper

 

 

OFC

Ð Outdoor Fan Contactor

 

 

 

VFD

Ð Variable Frequency Drive

 

 

Air Pressure Tubing Ð Before options such as inlet guide vanes (IGV), variable frequency drive (VFD), and/or modulating power exhaust can operate properly, the pneu- matic tubing for pressure sensing must be installed. Use ®re- retardent plenum tubing (®eld-supplied). Tubing size depends on type of control device (see Table 8 below). Tubing must be run from the appropriate sensing location (in the duct or in the building space) to the control device location in the unit.

Table 8 Ð Tubing Size

OPTION

UNITS

NOMINAL TUBE

SIZE (in.)

 

 

Inlet Guide Vanes (IGV)

ALL

3¤8

Variable Frequency

ALL

1¤4

Drive (VFD)

 

 

Modulating Power Exhaust

FK,FKX,JK,JKX

3¤8

INLET GUIDE VANES Ð The tubing for the duct pressure (DP) control option should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.

The inlet guide vanes are controlled by a differential pres- sure switch (DPS). On sizes 034-048, the DPS is located in the auxiliary control box at the economizer end of the unit (see Fig. 33). On sizes 054-104, the DPS is located in the supply fan section. See Fig. 34. Use a nominal 3¤8-in. plastic tubing.

VARIABLE FREQUENCY DRIVE Ð The tubing for the duct pressure (DP) control option should sample supply duct pressure about 2¤3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.

The duct pressure is sensed by a pressure transducer. The pressure transducer output is directed to the VFD. On 034- 048 units the DP transducer is located in the auxiliary con- trol box. On 054-104 units, the DP transducer is located in the supply fan section. See Fig. 34. Use a nominal 1¤4-in. plastic tubing.

23

Image 23
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsEXV Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input DIPRNT Ð Return Status Switch InputsConnector J2 Status Switch Unit Size Terminal no 034-104Page IFC Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal HIRCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsTerminal Block DPS Ð Differential Pressure SwitchSwitch START-UP Modulating Power Exhaust Differential Pressure Switch SizesConguration Header Jumpers Conguration Header DIP Switch Factory SettingsPotentiometer Inputs and Ranges Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorPressure VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command Control Signal Pressure VFD SET PointStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Normal Test Description Relay Number Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Description Thermistor or TestSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 104 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 088 UnitsOperation Status Codes TroubleshootingControls Troubleshooting Symptoms Probable Causes SolutionsDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP6 Terminals Voltage ACTest PIN Voltage DC TP3 TP4PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPIN Voltage Terminal Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages Terminal Strip J6 Connection Resistance ReadingQuick Test J5 PIN Numbers Step no Terminal Strip J5 Connector Resistance ReadingEnthalpy Sensor Checkout Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsMTR ALMLAT LPSPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP