Carrier 50FK, JK034-074, 48FK specifications Single-Step Demand Limit

Page 19

Connect the potentiometer end terminals to terminals 8 and 9 on control terminal block TB3 (sizes 034-048) or TB4 (sizes 054-104) (see Fig 27). Connect the switch terminals to the potentiometer wiper arm terminal and to terminal 10 on TB3 or TB4.

To enable demand limit function, change DIP switch 5 to position ON. (Disconnect control power before changing DIP switch positions. Reconnect power after all changes have been made.)

Set the potentiometer P4 to desired capacity reduction value.

Two-Step Demand Limit Ð Install the demand limit con- trol module (DLCM) according to the installation instruc- tions provided with the accessory. Disconnect existing leads at connector J3 on the processor board (see instructions) and connect the plug from the DLCM harness to connector J3.

Connect the ®eld input control power wires (from the ex- ternal control relays) at the terminal strips marked IN1, RTN1, IN2 and RTN2 (see Fig. 28 and 29).

To enable demand limit function, change DIP switch 5 to position ON. (Disconnect control power before hanging DIP switch positions. Reconnect power after all changes have been made.)

Set the potentiometers DLCM-P1 and DLCM-P2 to de- sired capacity reduction values.

Check the operation of demand limit function by using the Quick Test procedures.

CONFIGURATION

Single-Step Demand Limit Ð Field-installed potentiom- eter P4 establishes capacity reduction value for demand limit operation. Set this potentiometer between 0% and 100%. The exact percentage of capacity reduction differs depending on the number of capacity steps.

Two-Step Demand Limit Ð Potentiometer P1 and P2 (lo- cated on the accessory demand limit control module) estab- lish the capacity reduction values for each step of demand limit. Set potentiometer DLCM-P1 between 50% and 100%. Set potentiometer DLCM-P2 between 0% and 49%. The ex- act percentage of capacity reduction differs depending on the number of capacity steps.

OPERATING SEQUENCE

Single-Step Demand Limit Ð If the ®eld control switch to the wiper arm terminal is open, all capacity stages will be available (no demand limit in effect). When the ®eld control switch is closed, the compressor cooling capacity is reduced by the amount set on potentiometer P4.

When demand limit is in effect, the LED display will show

code 22 . If a potentiometer setting or input is out of range,

the control will terminate the demand limit function and show

code 84 at the display LED.

Two-Step Demand Limit Ð If the ®eld control switches are both open (no power supplied to the Demand Limit Control Module), all capacity stages will be available (no demand limit in effect). When control power is supplied to terminal IN1 only (®eld switch SW1 closes), the ®rst step of the de- mand limit is energized and the compressor cooling capacity is reduced by the amount set on potentiometer DLCM-P1. When control power is supplied to terminal IN2 (®eld switch SW2 closes), the second step of the demand limit is ener- gized and compressor cooling capacity is reduced by the amount set on potentiometer DLCM-P2.

When demand limit is in effect, the LED display will show code 22 . If a potentiometer setting or input is out of range, the control will terminate the demand limit function and show code 84 at the display LED.

034-048: TB3

054-104: TB4

8

 

9

5-20K

POTENTIOMETER

 

(P4)

10

SWITCH

Fig. 27 Ð Single-Step Demand Limit

Fig. 28 Ð Two-Step Demand Limit Module

NOTES:

1.Demand limit switches are ®eld supplied and wired.

2.Demand limit control module terminal blocks will accept up to 12-gage wire.

3.is ®eld wiring.

Fig. 29 Ð 115-Volt Field Wiring to Accessory

2-Step Demand Limit Control Module

Control From Remote Building Management Sys- tem (BMS) Ð The unit control system is not a commu- nicating control system, and it cannot be accessed directly by a DDC (Direct Digital Control) control system (or by a BACnet communication system). However, it is possible to control some functions of these units via 4 to 20 mA or 2 to 10 vdc signals and discrete inputs (relay contact closures).

Functions that can be managed from or accessed from an external control system include:

·Occupied/Unoccupied Status

·Night Setback Control

·Unit Supply Air Set Point Adjustment

·Demand Limit (1-stage or 2-stage)

·Supply Duct Pressure Set Point Adjustment

·External Alarm Signal

Remote control of the economizer cycle on these units is not recommended. Refer to the Operating Sequence section on page 35 for a discussion on the economizer cycle operation.

19

Image 19
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsEXV Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input DIPRNT Ð Return Status Switch InputsConnector J2 Status Switch Unit Size Terminal no 034-104Page IFC Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal HIRCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsSwitch DPS Ð Differential Pressure SwitchTerminal Block START-UP Modulating Power Exhaust Differential Pressure Switch SizesPotentiometer Inputs and Ranges Conguration Header DIP Switch Factory SettingsConguration Header Jumpers Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorPressure VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command Control Signal Pressure VFD SET PointStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Normal Test Description Relay Number Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Description Thermistor or TestSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 104 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 088 UnitsOperation Status Codes TroubleshootingControls Troubleshooting Symptoms Probable Causes SolutionsDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP6 Terminals Voltage ACTest PIN Voltage DC TP3 TP4PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPIN Voltage Terminal Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages Terminal Strip J6 Connection Resistance ReadingEnthalpy Sensor Checkout Terminal Strip J5 Connector Resistance ReadingQuick Test J5 PIN Numbers Step no Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsMTR ALMLAT LPSPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP