Carrier 48FK, JK034-074, 50FK specifications

Page 47

Incorrect Potentiometer Setting Ð A potentiometer turned fully clockwise or counterclockwise is outside the valid range and will result in a failure.

Faulty Wiring Ð If the wiring between the potentiometer and the processor board is incorrect, a failure will result.

Potentiometer Failure Ð If potentiometer is shorted or open, a failure will occur.

CODE 85: DEMAND LIMIT POTENTIOMETER (P4) FAIL- URE Ð Used only if demand limit is being used. If demand limit is used, DIP switch 5 must be in the ON position.

Two types of demand limit are available: a ®eld-supplied and installed single-step control consisting of a 10 Kohm, 3-wire linear potentiometer and an accessory 2-step control are available from Carrier. The single-step control has a single potentiometer while 2-step control has 2 potentiometers (mounted on the demand limit board, see Fig. 26).

For both types of demand limit, the control uses only 80% of the total potentiometer resistance. If resistance of poten- tiometer is less than 10% or greater than 90%, alarm light

will be energized, a diagnostic code of 85 will be displayed

when the display button is pushed, and demand limit will be terminated. If a failure occurs, it is probably due to one of the following:

Potentiometer Failure Ð If a potentiometer is shorted or open, a failure will occur.

Incorrect Potentiometer Setting Ð A potentiometer turned fully clockwise or counterclockwise will put potentiometer out of range resulting in an error.

Faulty Wiring Ð If wiring between the potentiometer and the processor board is incorrect, an error will occur.

DIP Switch 5 Ð If DIP switch 5 is in the ON position and potentiometer is not installed, an error will occur.

CODE 86: MINIMUM POSITION ECONOMIZER PO- TENTIOMETER FAILURE Ð If potentiometer P5 (on ac- cessory board) setting is less than 0% or greater than 100%,

alarm light will be energized, a code of 86 will be dis-

played when display button is pushed and economizer out- door air dampers will move to the fully closed position.

The potentiometer full-scale resistance is 10 Kohm, but when installed in parallel with the other 2 potentiometers on the accessory board, measured resistance will be 3.3 Kohm.

This failure will automatically reset when potentiometer returns to normal.

If a failure occurs, one of the following is the probable cause:

DIP Switch 3 Ð If this switch is in the ON position and the accessory board is not installed (accessory board is standard on these units, so it should always be on the unit).

Incorrect Potentiometer Setting Ð If potentiometer is turned fully clockwise or counterclockwise, potentiometer will be out of the allowable range, and an error will result.

Faulty Wiring Ð If wiring between the potentiometer and the processor board is incorrect, an error will occur.

Potentiometer Failure Ð If potentiometer is shorted or open, potentiometer will be out of range and an error will result.

CODE 87: WARM-UP TEMPERATURE SET POINT FAIL- URE Ð Applicable only if morning warm-up is used. Whether or not unit is equipped with electric resistance heaters, use of the morning warm-up function is recommended if the unit is shut down at night or over weekends. In this application, cooling will remain off and the outdoor-air damper will stay closed until heat load from the occupied space elevates return- air temperature to the warm-up set point. If warm-up func- tion is used, DIP switch 4 must be in the ON position. The

potentiometer (P6) is located on the accessory board. If po- tentiometer is set at less than 0° F or more than 95 F, alarm

light will be energized, a diagnostic code of 87 will ap- pear on the display when display button is pushed, and con- trol will use a default value of 40 F. If setting is between 0° F and 40 F, control will use a value of 40 F but no di- agnostic code will be displayed; if setting is between 80 F and 95 F, control will use a value of 80 F but no diagnostic code will be displayed.

The potentiometer full-scale resistance is 10 Kohm, but when wired in parallel with other potentiometers on the ac- cessory board, measured resistance is 3.3 Kohm.

The failure will automatically reset once potentiometer re- turns to normal. If a failure occurs, one of the following is the probable cause:

DIP Switch 4 Ð If this switch is in the ON position and the accessory board is not installed (accessory board is standard on these units, so it should always be on the unit).

Incorrect Potentiometer Setting Ð If potentiometer is turned fully clockwise or counterclockwise, potentiometer will be out of the allowable range, resulting in an error.

Faulty Wiring Ð If the wiring between the potentiometer and the processor board is incorrect, an error will occur.

Potentiometer Failure Ð If potentiometer is shorted or open, potentiometer will be out of range, resulting in an error.

Thermistor Troubleshooting Ð The VAV control sys- tem uses thermistors to measure temperatures of the enter- ing and supply air, as well as the saturated condensing tem- peratures of the refrigerant circuits. The resistance versus temperature and electrical characteristics for all thermistors in the system are identical. To obtain an accurate reading, a high-impedance meter (such as a digital meter) must be used.

Thermistors in the VAV control system have a 5 vdc sig- nal applied across them any time the unit control circuit is energized. The voltage drop across the thermistor is di- rectly proportional to the temperature and resistance of the thermistor.

To determine temperatures at the various thermistor lo- cations, disconnect the thermistor from the processor board and measure the resistance across the appropriate thermistor using a high-quality digital ohmmeter. Use the resistance read- ing to determine the thermistor temperature.

The microprocessor has been programmed to check the operation of the thermistors. If the measured temperature is outside of the range of −24 to 225 F or 98,010 to 282 ohms, then it will be treated as a sensor failure and a diagnostic code will be displayed. See Table 17 for sensor temperatures versus resistance drop. It is also possible to check the op- eration of the thermistors using the quick test routine.

If a thermistor has failed or the wire is damaged, replace the complete assembly. Do not attempt to spice the wires or repair the assembly.

Electronic Controls Checkout Ð The following will help determine whether a processor board, a relay board, dis- play set point board, accessory board, or 2-step demand limit module is faulty.

Before checking out any board, do the following:

1.At initial start-up, enter the Quick Test mode. This test will determine if all components are connected and op- erating properly.

2.If system has been operating and a malfunction occurs, check display for diagnostic codes. Use diagnostic chart located on inner panel of access door to control box sec- tion of unit; this chart will help determine probable cause of failure.

47

Image 47
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsEXV Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input DIPRNT Ð Return Status Switch InputsConnector J2 Status Switch Unit Size Terminal no 034-104Page IFC Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal HIRCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsTerminal Block DPS Ð Differential Pressure SwitchSwitch START-UP Modulating Power Exhaust Differential Pressure Switch SizesConguration Header Jumpers Conguration Header DIP Switch Factory SettingsPotentiometer Inputs and Ranges Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorPressure VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command Control Signal Pressure VFD SET PointStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Normal Test Description Relay Number Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Description Thermistor or TestSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 104 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 088 UnitsOperation Status Codes TroubleshootingControls Troubleshooting Symptoms Probable Causes SolutionsDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP6 Terminals Voltage ACTest PIN Voltage DC TP3 TP4PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPIN Voltage Terminal Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages Terminal Strip J6 Connection Resistance ReadingQuick Test J5 PIN Numbers Step no Terminal Strip J5 Connector Resistance ReadingEnthalpy Sensor Checkout Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsMTR ALMLAT LPSPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP