Carrier JK034-074, 50FK Terminal Strip J5 Connector Resistance Reading, Enthalpy Sensor Checkout

Page 51

Table 27 Ð Terminal Strip J5 Connector

Resistance Reading

QUICK TEST

 

J5 PIN NUMBERS

 

STEP NO.

1

2

3

4

5

1. to 2.5.

`

`

`

`

0

2.6

0

0

`

`

0

2.7.

0

`

0

`

0

2.8.

0

`

`

0

0

2.9. to 3.3.

0

`

`

`

0

 

 

 

 

 

 

LEGEND

` Ð In®nity

Step 2 Ð Check the Display LEDs

1.Enter Quick Test mode.

2.If 88 is not displayed, replace display board.

Step 3 Ð Check Set Point Potentiometer Ð Advance the dis- play to quick test step 1.9. to determine if this potentiometer is set and connected properly.

Step 4 Ð Check Display Switch Ð Press switch. If switch does not click, it is faulty and the display will be energized continuously. The switch is an integral part of display board and cannot be replaced separately.

ACCESSORY BOARD CHECKOUT Ð The accessory board can be completely checked using quick test steps 2.0., 2.2., and 2.3. It can also be checked out as follows:

1.Remove the accessory board connector from the proces- sor board and connect an ohmmeter to terminals 3 and 4 on the connector. Numbers are marked on the connector. See Fig. 15.

2.Set the meter to 10,000 ohms. The resistance value ob- tained should be 3,333 ohms. Adjust the potentiometers and the resistance value should not change.

3.Connect the ohmmeter to terminals 3 and 6. As the reset limit potentiometer is turned clockwise, resistance should increase from 0 to approximately 3,400 ohms.

4.Connect the ohmmeter to terminals 3 and 5. As the econo- mizer minimum position potentiometer is turned clock- wise, resistance should increase from 0 to approximately 3,400 ohms.

5.Connect the ohmmeter to terminals 3 and 2. As the warm-up set point potentiometer is turned clockwise, resistance should increase from 0 to approximately 3,400 ohms.

If any of the Steps 1 through 5 result in any other ohm reading, replace the board; it cannot be serviced.

TWO-STEP DEMAND LIMIT CONTROL MODULE (DLCM) TROUBLESHOOTING Ð If a problem is suspected in the DLCM board, use the following test procedure:

The board can only be checked when it is connected to the processor and the processor is energized so that the DLCM is supplied with 5 vdc power. The terminals referenced are shown in Fig. 16. Potentiometers P1 and P2 refer to the DLCM potentiometers.

IMPORTANT: Be careful to avoid damaging the con- nector or the processor board when taking the voltage readings.

Test under the following conditions:

·No power to IN1 or IN2

Terminal 1 to 2 should read 4.5 vdc ±0.1 v Terminal 2 to 3 should read 5.0 vdc ±0.1 v

·Power to IN2 or to both IN1 and IN2, and P2 set at 24% Terminal 1 to 2 should read 1.5 vdc ± 0.1 v

NOTE: Voltage should vary between 0.5 vdc and 2.5 vdc as the setting of P2 is varied between 0% and 49%.

Terminal 2 to 3 should read 5.0 vdc ± 0.1 v

·Power to IN1 only and P1 set at 50% Terminal 1 to 2 should read 2.5 vdc ± 0.1 v Terminal 2 to 3 should read 5.0 vdc ± 0.1 v

NOTE: Voltage should vary between 0.5 vdc and 2.5 vdc as the setting of P2 is varied between 50% and 100%.

NOTE: If the voltages listed in these 3 tests are not obtained during testing, the DLCM board must be replaced.

Enthalpy Sensor Checkout Ð To test operation of enthalpy sensor, see Table 28.

Table 28 Ð Enthalpy Sensor Checkout

TEST

EXPECTED RESULT

 

AND RESPONSE

Outdoor-air sensor:

 

Enthalpy sensor + terminal

Milliammeter reading should be

should be connected to +

between 3 and 24 mA if sensor

terminal on motor. Connect the

is operating correctly. If reading

positive terminal of a DC

is 0 mA, the sensor is either

milliammeter to the S terminal

wired backwards or is defective.

of the sensor and the negative

 

terminal of the meter to SO

 

terminal of the enthalpy board.

 

Indoor-air sensor:

Milliammeter reading should be

Enthalpy sensor + terminal

between 3 and 24 mA if sensor

should be connected to +

is operating correctly. If reading

terminal on motor. Connect the

is 0 mA, the sensor is either

positive terminal of a DC

wired backwards or is defective.

milliammeter to the S terminal

 

of the sensor and the negative

 

terminal of the meter to SR

 

terminal of the enthalpy board.

 

51

Image 51
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsEXV Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input DIPRNT Ð Return Status Switch InputsConnector J2 Status Switch Unit Size Terminal no 034-104Page IFC Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal HIRCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsDPS Ð Differential Pressure Switch SwitchTerminal Block START-UP Modulating Power Exhaust Differential Pressure Switch SizesConguration Header DIP Switch Factory Settings Potentiometer Inputs and RangesConguration Header Jumpers Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorPressure VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command Control Signal Pressure VFD SET PointStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Normal Test Description Relay Number Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Description Thermistor or TestSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 104 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 088 UnitsOperation Status Codes TroubleshootingControls Troubleshooting Symptoms Probable Causes SolutionsDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP6 Terminals Voltage ACTest PIN Voltage DC TP3 TP4PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPIN Voltage Terminal Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages Terminal Strip J6 Connection Resistance ReadingTerminal Strip J5 Connector Resistance Reading Enthalpy Sensor CheckoutQuick Test J5 PIN Numbers Step no Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsMTR ALMLAT LPSPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP