LEGEND

ECON Ð Economizer

MIN Ð Minimum

PÐ Potentiometer

VAV Ð Variable-Air Volume

Fig. 15 Ð Accessory Relay Board

(Standard; Factory Supplied)

 

 

LEGEND

IC

Ð

Integrated Circuit

IN

Ð

Input

PÐ Potentiometer RTN Ð Return

Fig. 16 Ð Two-Step Demand Limit Module

Fig. 17 Ð Enthalpy Sensor Location

Variable Frequency Drive (VFD) Ð The optional VFD is used to modulate supply fan air¯ow to maintain duct static pressure on VAV applications. The VFD is located in the supply fan section (see Fig. 18 and 19), and can be ac- cessed by opening the fan section access door.

The unit is supplied with a pressure transducer capable of measuring from 0.0 to 5.0 in. wg. The pressure transducer will send a 4 to 20 mA signal to the VFD to modulate the speed of the indoor fan motor to precisely control the fan to the desired static pressure set point. The VFD is factory set at 2.5 in. wg duct static pressure. Refer to the Operating Se- quence section for more information on the VFD.

The VFD has been programmed and wired at the factory for this application. No further adjustments (except for Duct Static Pressure Set Point) should be necessary at start-up. Factory jumper wire con®gurations are shown in the Supply Fan Control with VFD Option section on page 28.

A separate service manual for the factory-installed VFD is supplied with each unit. Refer to the VFD manual for more information on the VFD controls.

Temperature Reset Ð Accessory temperature reset al- lows the unit to automatically adjust (``reset'') the supply- air temperature set point to a higher value once most of the space cooling load has been met. When the space conditions are satis®ed, the VAV terminals will close to the minimum position. All VAV units will sense the decrease in actual supply- air temperature and the unit controls respond by reducing

Fig. 18 Ð Variable Frequency Drive,

Sizes 034-048 and 078-104

Fig. 19 Ð Variable Frequency Drive, Sizes 054-074

12

Image 12
Contents Controls Operation Troubleshooting ContentsSafety Considerations GeneralPin Terminal Connector J1 Thermistor Inputs Connector J1 Temperature Unit Size Terminal no InputDIP EXVStatus Switch Inputs Connector J2 Status Switch Unit Size Terminal no034-104 RNT Ð ReturnPage Output Pin and Terminal Assignments Output PIN Name Rating Device TerminalHIR IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Integrated Circuit InputControls Installation Space Temperature ResetUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Voltage Drop Characteristics Thermistor ResistanceSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Switches Required for Each Mode Smoke Control ModesSwitch Functions Tubing SizeDPS Ð Differential Pressure Switch SwitchTerminal Block Modulating Power Exhaust Differential Pressure Switch Sizes START-UPConguration Header DIP Switch Factory Settings Potentiometer Inputs and RangesConguration Header Jumpers DIP Switches Switch Function Meaning PositionInlet Guide Vane Motor 50FK,JK034-074 Units Jumper Removal to Disable Motor Variable Frequency Drive KeypadVFD Set Point Frequency Command for Duct Pressure Changing the VFD Set Point Frequency CommandControl Signal Pressure VFD SET Point PressureStart Unit Quick Test, Unit Conguration and Switch Check Quick Normal Description Control Switch Test Display Step noQuick Test, Thermistor and Potentiometer Check Quick Test, Output Relay CheckQuick Normal Description Thermistor or Test Quick Normal Test Description Relay NumberOperating Information Sensor Resistance ValuesPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 054 Units Cooling Size 064 UnitsCooling Size 088 Units Cooling Size 104 UnitsTroubleshooting Controls TroubleshootingSymptoms Probable Causes Solutions Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page Terminals Voltage AC Test PIN Voltage DC TP3TP4 TP6Quick Test J9 PIN Numbers Step no PIN Terminal Voltage DCPin Terminal Connector J1 Voltages Pin Terminal Connector J2 VoltagesTerminal Strip J6 Connection Resistance Reading PIN Voltage TerminalTerminal Strip J5 Connector Resistance Reading Enthalpy Sensor CheckoutQuick Test J5 PIN Numbers Step no Variable Frequency Drive Carrier Default Program Parameter Values Parameter Group Default ValueRequired User Adjusted Defaults Motor Overload SettingsALM LATLPS MTRPage Page Service Training Call for Free CatalogII. Preliminary Checklist Items PRE-START-UPIII. START-UP IV. Notes