Carrier 48FK, JK034-074 Pin Terminal Connector J1 Voltages, Pin Terminal Connector J2 Voltages

Page 50

Table 24 Ð Pin Terminal Connector J1 Voltages

PIN

VOLTAGE

TERMINAL

(vdc ± 0.25 v)

1

0

2

5

6

0

7

5

8

0

9

5

10

0

11

5

12

0

13

5

14

0

15

5

16

0

17

5

18

0

19

5

20

0

21

5

Step 9 − Thermistor Input Connector Checkout

1.Turn power to OFF position.

2.Disconnect all plugs for pin terminal connector J2 and mark them for later replacement.

3.Connect a negative test lead to test pin TP18.

4.Turn power to ON position, and enter the Quick Test routine.

5.Place the other lead on terminals shown in Table 25, and check the voltages.

6.If voltages are incorrect (per Table 25), replace processor board.

7.Turn power to OFF position, and replace the plugs re- moved in Step 2.

8.Turn power to ON position.

Table 25 Ð Pin Terminal Connector J2 Voltages

PIN

VOLTAGE

TERMINAL

(vdc ± 0.25 v)

1

0

2

5

3

0

4

5

7

0

8

5

9

0

10

5

13

0

14

5

15

5

17

5

18

5

19

5

20

5

21

5

22

5

23

5

24

5

If Steps 1 through 9 have been competed and the unit still will not function properly, replace the processor board.

RELAY BOARD TROUBLESHOOTING Ð The relay board contains 13 electromechanical relays. The small relays are 24 vac, and the large relays are 115 vac. These relays are controlled by the processor through the ribbon cable at- tached to the relay board.

The following procedure can be used to check out the op- eration of the relays. To do this, turn the control ON/OFF switch to the OFF position, and remove the wiring connec- tors connected to pin terminal connectors J5 and J6. Set the meter for resistance. If the contacts do not close at the re- quired quick test step, check the relay outputs from the pro- cessor board.

Relay Board Checkout (Fig. 5)

Step 1 Ð Low-voltage relay resistance check.

1.Turn switch to OFF position.

2.Remove plug connection from terminal strip J6.

3.Set meter to measure resistance. Connect negative test lead to both terminals 11 and 12 of J6.

4.Turn switch to ON position and go into quick test mode.

5.Place other meter lead on terminals shown in Table 26 and check resistances at each quick test step.

6.If these resistances are not correct and relay board out- puts from processor board have been checked out, re- place relay board.

Step 2 Ð High-voltage relay resistance check.

1.Turn switch to OFF position.

2.Remove plug connection from terminal connector J5.

3.Connect negative test lead to terminal 8.

4.Check the resistance between terminals 8 and 5 before entering Quick Test mode. The resistance should be in®nity.

5.Turn switch to ON position and go into Quick Test mode.

6.Place other meter lead on terminals shown in Table 27 and check resistance at each quick test step.

7.If these resistances are not correct and relay board out- puts from processor board have been checked per Pro- cessor Board Checkout section on page 48, replace relay board.

DISPLAY BOARD CHECKOUT

Step 1 Ð Check the Output Voltage from Processor Board to the Relay Board Ð Refer to Step 6 Ð Display Board Con- nection Checkout section on page 49.

Table 26 Ð Terminal Strip J6 Connection

Resistance Reading

QUICK TEST

 

 

J6 PIN NUMBERS

 

 

 

STEP NO.

1

2

3

4

5

 

6

7

8

1. to 2.3.

`

`

`

`

`

 

`

`

`

2.4.

`

`

`

`

`

 

`

0

`

2.5.

`

`

`

`

`

 

`

`

0

2.6.

`

`

`

`

`

 

`

`

`

2.7.

`

`

`

`

`

 

`

`

`

2.8.

`

`

`

`

`

 

`

`

`

2.9.

0

`

`

`

`

 

`

`

`

3.0.

`

0

`

`

`

 

`

`

`

3.1.

`

`

0

`

`

 

`

`

`

3.2.

`

`

`

`

0

 

`

`

`

3.3.

`

`

`

`

`

 

0

`

`

 

 

 

 

 

 

 

 

 

 

LEGEND

` Ð In®nity

NOTE: Pins shown in boldface type will be energized for only 10 seconds. All other pins will be energized continuously while at the proper quick test step. The control will remain in the Quick Test mode for only 10 minutes unless the display button is pressed.

50

Image 50
Contents Controls Operation Troubleshooting ContentsSafety Considerations GeneralDIP Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input EXV034-104 Status Switch InputsConnector J2 Status Switch Unit Size Terminal no RNT Ð ReturnPage HIR Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Integrated Circuit InputControls Installation Space Temperature ResetUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Voltage Drop Characteristics Thermistor ResistanceSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Switches Required for Each Mode Smoke Control ModesSwitch Functions Tubing SizeTerminal Block DPS Ð Differential Pressure SwitchSwitch Modulating Power Exhaust Differential Pressure Switch Sizes START-UPConguration Header Jumpers Conguration Header DIP Switch Factory SettingsPotentiometer Inputs and Ranges DIP Switches Switch Function Meaning PositionInlet Guide Vane Motor 50FK,JK034-074 Units Jumper Removal to Disable Motor Variable Frequency Drive KeypadControl Signal Pressure VFD SET Point VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command PressureStart Unit Quick Test, Unit Conguration and Switch Check Quick Normal Description Control Switch Test Display Step noQuick Normal Description Thermistor or Test Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Test Description Relay NumberOperating Information Sensor Resistance ValuesPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 088 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 104 UnitsSymptoms Probable Causes Solutions TroubleshootingControls Troubleshooting Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP4 Terminals Voltage ACTest PIN Voltage DC TP3 TP6Quick Test J9 PIN Numbers Step no PIN Terminal Voltage DCTerminal Strip J6 Connection Resistance Reading Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages PIN Voltage TerminalQuick Test J5 PIN Numbers Step no Terminal Strip J5 Connector Resistance ReadingEnthalpy Sensor Checkout Variable Frequency Drive Carrier Default Program Parameter Values Parameter Group Default ValueRequired User Adjusted Defaults Motor Overload SettingsLPS ALMLAT MTRPage Page Service Training Call for Free CatalogII. Preliminary Checklist Items PRE-START-UPIII. START-UP IV. Notes