Carrier 50FK, JK034-074, 48FK Smoke Control Modes, Smoke Control Switches Required for Each Mode

Page 22

INSTALLATION Ð To enable one or more of the possible smoke control modes available with these units, determine the switches required for the desired mode(s) from Table 6, ®eld-supply and install the appropriate switches and ®eld wire per Fig. 32. Switch functions are shown in Table 7.

Table 5 Ð Smoke Control Modes

 

 

MODE

 

 

FUNCTION

Fire

Pressur-

Evacuation*

 

Smoke

 

Shutdown

ization

 

Purge*

 

 

 

Supply Fan

Off

On

Off

 

On

IGV/VFD²

Ð

Open/On

Ð

 

Open/On

Economizer

Closed

Open

Open

 

Open

Return Air

Open

Closed

Closed

 

Closed

Damper

 

 

 

 

 

 

Exhaust

Off

Off

On

 

On

Fans

 

 

 

 

 

 

Exhaust

Closed

Closed

Open

 

Open

Damper

 

 

 

 

 

 

LEGEND

 

 

 

 

IGV Ð Inlet Guide Vane

VAV Ð Variable Air Volume

VFD Ð Variable Frequency Drive

*Power exhaust option/accessory required for this mode. ²Applicable to VAV units with appropriate options.

CONFIGURATION Ð No set points required for Smoke Con- trol modes. Modes are activated by energizing all switches appropriate for each Smoke Control mode.

OPERATING SEQUENCE

Fire Shutdown Ð At command from the ®eld switches (see Table 5), all unit operation (cooling, heating, supply fan and power exhaust) will terminate.

Pressurization Ð At command from the ®eld switches for Pressurization mode (see Table 5):

1.Economizer dampers will open

2.The HIR function will energize, opening room terminals to full-open (heating) positions.

3.Supply fan will run. (If equipped with IGV: control vanes

will open. If equipped with VFD: the VFD will control to duct static set point or best available with all terminals open.)

4.Power exhaust dampers (if equipped) will close.

5.Power exhaust fans (if equipped) will turn off.

Evacuation Ð At command from the ®eld switches for Evacu- ation mode (see Table 5):

1.Supply fan will turn off.

2.Economizer dampers will open.

3.Exhaust fans will run at maximum capacity.

4.Exhaust dampers will open.

Smoke Purge Ð At command from the ®eld switches for Smoke Purge mode (see Table 5):

1.Economizer dampers will open.

2.The HIR function will energize, opening room terminals to full-open (heating) positions.

3.Supply fan will run. (If equipped with IGV: Control vanes

will open. If equipped with VFD: the VFD will control to duct static set point or best available with all terminals open.)

4.Exhaust fans will run at maximum capacity.

5.Exhaust dampers will open.

Table 6 Ð Smoke Control Switches Required for Each Mode

FIRE

 

EVACUATION

SMOKE

PRESSURIZATION

(Modulating Power

SHUTDOWN

PURGE

 

Exhaust)

 

 

 

SW-1

SW-1

SW-1

SW-1

SW-2

SW-2

SW-2

SW-2

 

SW-4

SW-3

SW-3

 

SW-5

SW-5

SW-4

 

SW-6

SW-6

SW-9A/B

 

SW-9A/B

SW-7

 

 

 

SW-8

 

 

 

 

 

NOTE: All switches are shown in ``as installed'' (power OFF or deenergized) position. In these positions, none of these modes will be activated; normal unit operation is permitted by the base unit controls. To initiate any mode, all switches listed under this mode in the table must be energized, causing the depicted contact position to change from depicted positions to energized positions. Switches may be manually or electrically operated.

22

Image 22
Contents Controls Operation Troubleshooting ContentsSafety Considerations GeneralDIP Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input EXV034-104 Status Switch InputsConnector J2 Status Switch Unit Size Terminal no RNT Ð ReturnPage HIR Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Integrated Circuit InputControls Installation Space Temperature ResetUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Voltage Drop Characteristics Thermistor ResistanceSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Switches Required for Each Mode Smoke Control ModesSwitch Functions Tubing SizeSwitch DPS Ð Differential Pressure SwitchTerminal Block Modulating Power Exhaust Differential Pressure Switch Sizes START-UPPotentiometer Inputs and Ranges Conguration Header DIP Switch Factory SettingsConguration Header Jumpers DIP Switches Switch Function Meaning PositionInlet Guide Vane Motor 50FK,JK034-074 Units Jumper Removal to Disable Motor Variable Frequency Drive KeypadControl Signal Pressure VFD SET Point VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command PressureStart Unit Quick Test, Unit Conguration and Switch Check Quick Normal Description Control Switch Test Display Step noQuick Normal Description Thermistor or Test Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Test Description Relay NumberOperating Information Sensor Resistance ValuesPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 088 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 104 UnitsSymptoms Probable Causes Solutions TroubleshootingControls Troubleshooting Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP4 Terminals Voltage ACTest PIN Voltage DC TP3 TP6Quick Test J9 PIN Numbers Step no PIN Terminal Voltage DCTerminal Strip J6 Connection Resistance Reading Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages PIN Voltage TerminalEnthalpy Sensor Checkout Terminal Strip J5 Connector Resistance ReadingQuick Test J5 PIN Numbers Step no Variable Frequency Drive Carrier Default Program Parameter Values Parameter Group Default ValueRequired User Adjusted Defaults Motor Overload SettingsLPS ALMLAT MTRPage Page Service Training Call for Free CatalogII. Preliminary Checklist Items PRE-START-UPIII. START-UP IV. Notes