Table 18 Ð Sensor Resistance Values
TEMP | RESISTANCE | TEMP | RESISTANCE | TEMP | RESISTANCE |
(F) | (Ohms) | (F) | (Ohms) | (F) | (Ohms) |
−60 | 362,640 | 45 | 11,396 | 150 | 1,020 |
−55 | 297,140 | 50 | 9,950 | 155 | 929 |
−50 | 245,245 | 55 | 8,709 | 160 | 844 |
−45 | 202,841 | 60 | 7,642 | 165 | 768 |
−40 | 168,250 | 65 | 6,749 | 170 | 699 |
−35 | 139,960 | 70 | 5,944 | 175 | 640 |
−30 | 116,820 | 75 | 5,249 | 180 | 585 |
−25 | 98,420 | 80 | 4,644 | 185 | 535 |
−20 | 82,665 | 85 | 4,134 | 190 | 490 |
−15 | 69,685 | 90 | 3,671 | 195 | 449 |
−10 | 58,915 | 95 | 3,265 | 200 | 414 |
−5 | 50,284 | 100 | 2,913 | 205 | 380 |
0 | 42,765 | 105 | 2,600 | 210 | 350 |
5 | 36,475 | 110 | 2,336 | 215 | 323 |
10 | 31,216 | 115 | 2,092 | 220 | 299 |
15 | 26,786 | 120 | 1,879 | 225 | 276 |
20 | 23,164 | 125 | 1,689 | 230 | 255 |
25 | 19,978 | 130 | 1,527 | 235 | 236 |
30 | 17,276 | 135 | 1,377 | 240 | 219 |
35 | 14,980 | 140 | 1,244 |
|
|
40 | 13,085 | 145 | 1,126 |
|
|
|
|
|
|
|
|
3.Quick Test Steps 2.4.-3.3. Ð Output Relay Check
These quick test steps allow microprocessor to check output signals from relay boards in unit control system. In ad- dition, operation of all the condenser fans, compres- sors, and economizer (if equipped) are checked at each step.
Normal display for Steps 2.4. through 2.8. is 1. In Steps
2.9.through 3.2., each compressor and unloader is started and allowed to run for approximately 10 seconds. At start- up, a 0 will appear on the display followed by a 1 (Steps
2.9.and 3.2.) in a few seconds. Steps 3.0. and 3.1. will always be 0 since there are unloaders, and Step 3.3. will always be zero since it is not used.
At end of the
Fan and compressor operating sequence for quick test Steps 2.4. through 3.3. are shown in Table 17.
If the quick test steps do not operate as described above, a defect exists in one or more of the following: relay being tested, electronic control, or unit wiring. Determine problem and correct.
OPERATING INFORMATION
Digital Display Ð The VAV control system uses a
CODES 0 THROUGH 8, CAPACITY STEPS Ð These codes indicate the number of cooling stages active at the time the display button is pressed. The highest code indicated on the display will be 6 for the 034,038 and
Capacity steps are directly related to pin terminal connec- tor J6 output. At step zero, the unit has no mechanical cool- ing on, and the economizer may or may not be operating (depending on the outdoor air conditions). Once a cooling load is detected (T1 thermistor reads above the
load if the outdoor enthalpy is good. As long as the outdoor- air enthalpy is acceptable, no mechanical cooling will take place until the economizer dampers are fully open. The rest of the steps and the operational sequence vary due to the number of compressors and unloaders. Refer to Operating Sequence section on page 35 for the unit stages of operation.
CODES 20 THROUGH 30 AND 88, OPERATIONAL STA- TUS Ð These codes indicate special operational modes, such as initialization, morning
Initialization Ð When the control is turned on, the display shows a 20 for approximately 2 minutes to indicate that the
control is in the initialization mode. During this time, the economizer dampers open and close to determine the resis- tance range of the economizer position potentiometer (P2) for full economizer operation. The processor loads the nec- essary constants for proper unit operation and checks the ther- mistors and other potentiometers for their values and valid- ity. After the initialization period, the display screen goes blank until the display button is pressed. If the display but- ton is pressed during the
Temperature Reset Ð If the unit is equipped with the ac- cessory temperature reset package, and DIP switch 2 is in the ON position, the unit will reset the
Demand Limit Ð If the unit is equipped with the accessory demand limit control module or the
determined value. When this condition is in effect, a 22 will appear in the display.
Morning
routine. When this condition is in effect, a 26 will appear in the display.
Internal Failure Ð If the unit detects an internal fault (such as a time measurement failure), or detects an incorrect volt- age on an input channel, a 30 will be displayed, and the unit will shut down.
Quick Test Ð If the display button is pressed during the initialization period of the processor, the unit will run its self- diagnostic routine. When this is in effect, an 88 will appear in the display screen.
CODES 51 THROUGH 87, DIAGNOSTIC INFORMA- TION Ð These codes indicate diagnostic information when there is a unit problem such as a faulty thermistor, potenti- ometer, or compressor fault. Refer to Diagnostic Codes sec- tion on page 45 for more details. Codes 53, 54, 57, 58, 61, 62,
Under normal operation, only the stage number is dis- played when the display button is pressed. If a status or over- load code is displayed, the display will rotate every 2 sec- onds and will display up to 3 codes. Overload information takes priority over all other codes. The codes are stored in the microprocessor as long as the board remains energized.
34