Carrier JK034-074 Quick Test, Thermistor and Potentiometer Check, Quick Test, Output Relay Check

Page 33

Table 16 Ð Quick Test, Thermistor and Potentiometer Check

QUICK

NORMAL

 

DESCRIPTION

THERMISTOR OR

TEST

 

DISPLAY

 

POTENTIOMETER*

STEP NO.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Thermistor OK

Supply Air

 

1.4.

 

 

1

 

 

 

 

 

0

Ð Thermistor Faulty

Thermistor (T1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Thermistor OK

Return Air

 

1.5.

 

 

1

 

 

 

 

 

0

Ð Thermistor Faulty

Thermistor (T2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Thermistor OK

Circuit 1 Condenser Thermistor

 

1.6.

 

 

1

 

 

 

 

 

0

Ð Thermistor Faulty

(T3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Thermistor OK

Circuit 2 Condenser Thermistor

 

1.7.

 

 

1

 

 

 

 

 

0

Ð Thermistor Faulty

(T4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Thermistor or Potentiometer OK

Accessory Space Temperature Thermistor (T10)

 

1.8.

 

 

1

 

0 Ð Thermistor or Potentiometer Faulty or

 

 

 

 

or Accessory Reset Potentiometer (P7)

 

 

 

 

 

 

 

Option not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Potentiometer OK

Supply-Air Set Point

 

1.9.

 

 

1

 

 

 

 

 

0

Ð Potentiometer Faulty

Potentiometer (P1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Potentiometer OK

Accessory Reset Limit

 

2.0.

 

 

1

 

 

 

 

 

0

Ð Potentiometer Faulty or Option not used

Potentiometer (P3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Potentiometer OK

Accessory Demand Limit

 

2.1.

 

 

1

 

 

 

 

 

0

Ð Potentiometer Faulty or Option not used

Potentiometer (P4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Potentiometer OK

Minimum Position

 

2.2.

 

 

1

 

Economizer

 

 

 

 

0

Ð Potentiometer Faulty or Option not used

 

 

 

 

 

 

Potentiometer (P5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Ð Potentiometer OK

Warm-Up Set Point

 

2.3.

 

 

1

 

 

 

 

 

0

Ð Potentiometer Faulty or Option not used

Potentiometer (P6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Potentiometer P2 is not listed since it is not part of the quick test. If on unit start-up a Code 83 is displayed, check potentiometer P2.

Table 17 Ð Quick Test, Output Relay Check

QUICK

 

 

NORMAL

 

 

 

 

TEST

 

 

 

 

DESCRIPTION

RELAY NUMBER

 

 

DISPLAY

 

 

STEP NO.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.4.

 

 

 

 

1

 

 

 

1 Ð Open Economizer or Open Relay if no Economizer

K7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5.

 

 

 

 

1

 

 

 

1 Ð Close Economizer or Close Relay if no Economizer

K8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Ð Energize Fan Relay and Heat Relay

K9* and K10

 

2.6.

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.7.

 

 

 

 

1

 

 

 

Energize Stage 1 Condenser Fan(s)

K11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.8.

 

 

 

 

1

 

 

 

Energize Stage 2 Condenser Fan(s)

K12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.9.

 

 

0

then

1

then

0

 

Energize Compressor 1²

K1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0.

 

 

0

 

 

 

Energize Unloader 2; Not Used (044, 104)

K2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.1.

 

 

0

 

 

 

Energize Unloader 1

K3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2.

 

 

0

then

1

then

0

 

Energize Compressor 2²

K5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.3.

 

 

0

 

 

 

Not Used

K6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

CR Ð Control Relay

*K9 (fan relay) will remain on for duration of quick test.

²Compressor will be energized for 10 seconds. Zero indicates open CR; 1 indicates closed CR.

33

Image 33
Contents Contents Controls Operation TroubleshootingGeneral Safety ConsiderationsConnector J1 Temperature Unit Size Terminal no Input Pin Terminal Connector J1 Thermistor InputsDIP EXVConnector J2 Status Switch Unit Size Terminal no Status Switch Inputs034-104 RNT Ð ReturnPage Output PIN Name Rating Device Terminal Output Pin and Terminal AssignmentsHIR IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Input Integrated CircuitSpace Temperature Reset Controls InstallationUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Thermistor Resistance Voltage Drop CharacteristicsSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Modes Smoke Control Switches Required for Each ModeTubing Size Switch FunctionsDPS Ð Differential Pressure Switch SwitchTerminal Block START-UP Modulating Power Exhaust Differential Pressure Switch SizesConguration Header DIP Switch Factory Settings Potentiometer Inputs and RangesConguration Header Jumpers Switch Function Meaning Position DIP SwitchesInlet Guide Vane Motor 50FK,JK034-074 Units Variable Frequency Drive Keypad Jumper Removal to Disable MotorChanging the VFD Set Point Frequency Command VFD Set Point Frequency Command for Duct PressureControl Signal Pressure VFD SET Point PressureStart Unit Quick Normal Description Control Switch Test Display Step no Quick Test, Unit Conguration and Switch CheckQuick Test, Output Relay Check Quick Test, Thermistor and Potentiometer CheckQuick Normal Description Thermistor or Test Quick Normal Test Description Relay NumberSensor Resistance Values Operating InformationPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 064 Units Cooling Size 054 UnitsCooling Size 088 Units Cooling Size 104 UnitsControls Troubleshooting TroubleshootingSymptoms Probable Causes Solutions Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page Test PIN Voltage DC TP3 Terminals Voltage ACTP4 TP6PIN Terminal Voltage DC Quick Test J9 PIN Numbers Step noPin Terminal Connector J2 Voltages Pin Terminal Connector J1 VoltagesTerminal Strip J6 Connection Resistance Reading PIN Voltage TerminalTerminal Strip J5 Connector Resistance Reading Enthalpy Sensor CheckoutQuick Test J5 PIN Numbers Step no Variable Frequency Drive Parameter Group Default Value Carrier Default Program Parameter ValuesMotor Overload Settings Required User Adjusted DefaultsLAT ALMLPS MTRPage Page Call for Free Catalog Service TrainingPRE-START-UP II. Preliminary Checklist ItemsIV. Notes III. START-UP