Table 16 Ð Quick Test, Thermistor and Potentiometer Check
QUICK | NORMAL |
| DESCRIPTION | THERMISTOR OR | ||||
TEST |
| |||||||
DISPLAY |
| POTENTIOMETER* | ||||||
STEP NO. |
|
| ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Thermistor OK | Supply Air |
| 1.4. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Thermistor Faulty | Thermistor (T1) | ||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Thermistor OK | Return Air |
| 1.5. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Thermistor Faulty | Thermistor (T2) | ||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Thermistor OK | Circuit 1 Condenser Thermistor |
| 1.6. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Thermistor Faulty | (T3) | ||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Thermistor OK | Circuit 2 Condenser Thermistor |
| 1.7. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Thermistor Faulty | (T4) | ||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Thermistor or Potentiometer OK | Accessory Space Temperature Thermistor (T10) |
| 1.8. |
|
| 1 |
| 0 Ð Thermistor or Potentiometer Faulty or | ||
|
|
|
| or Accessory Reset Potentiometer (P7) | ||||
|
|
|
|
|
|
| Option not used | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Potentiometer OK | |
| 1.9. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Potentiometer Faulty | Potentiometer (P1) | ||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Potentiometer OK | Accessory Reset Limit |
| 2.0. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Potentiometer Faulty or Option not used | Potentiometer (P3) | ||
|
|
|
|
|
| |||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Potentiometer OK | Accessory Demand Limit |
| 2.1. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Potentiometer Faulty or Option not used | Potentiometer (P4) | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Potentiometer OK | Minimum Position |
| 2.2. |
|
| 1 |
| Economizer | ||
|
|
|
| 0 | Ð Potentiometer Faulty or Option not used | |||
|
|
|
|
|
| Potentiometer (P5) | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 | Ð Potentiometer OK | |
| 2.3. |
|
| 1 |
| |||
|
|
|
| 0 | Ð Potentiometer Faulty or Option not used | Potentiometer (P6) | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
*Potentiometer P2 is not listed since it is not part of the quick test. If on unit
Table 17 Ð Quick Test, Output Relay Check
QUICK |
|
| NORMAL |
|
|
|
| ||||
TEST |
|
|
|
| DESCRIPTION | RELAY NUMBER | |||||
|
| DISPLAY |
|
| |||||||
STEP NO. |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2.4. |
|
|
|
| 1 |
|
|
| 1 Ð Open Economizer or Open Relay if no Economizer | K7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 2.5. |
|
|
|
| 1 |
|
|
| 1 Ð Close Economizer or Close Relay if no Economizer | K8 |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1 Ð Energize Fan Relay and Heat Relay | K9* and K10 | ||
| 2.6. |
|
|
|
| 1 |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 2.7. |
|
|
|
| 1 |
|
|
| Energize Stage 1 Condenser Fan(s) | K11 |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 2.8. |
|
|
|
| 1 |
|
|
| Energize Stage 2 Condenser Fan(s) | K12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 2.9. |
|
| 0 | then | 1 | then | 0 |
| Energize Compressor 1² | K1 |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 3.0. |
|
| 0 |
|
|
| Energize Unloader 2; Not Used (044, 104) | K2 | ||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 3.1. |
|
| 0 |
|
|
| Energize Unloader 1 | K3 | ||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| 3.2. |
|
| 0 | then | 1 | then | 0 |
| Energize Compressor 2² | K5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 3.3. |
|
| 0 |
|
|
| Not Used | K6 | ||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
LEGEND
CR Ð Control Relay
*K9 (fan relay) will remain on for duration of quick test.
²Compressor will be energized for 10 seconds. Zero indicates open CR; 1 indicates closed CR.
33