Fig. 11 Ð Thermistor T2 Location, Size 034-048 Units
STANDARD FILTERS | BAG FILTERS |
|
Fig. 12 Ð Thermistor T2 Location, Size 054-104 Units
Economizer Ð Economizer control is used to control the outside and return air dampers of the unit, to satisfy space cooling demand using all outside air (when permitted), and to satisfy cooling in conjunction with compressor operation (when conditions permit). During Occupied periods without cooling demand, the
The economizer is available as a
Fig. 13 Ð Thermistor T3 and T4 Locations,
Size 034-048 Units
ENTHALPY CONTROL Ð Outside air enthalpy control is standard with the
DIFFERENTIAL ENTHALPY Ð Added efficiencies in econo- mizer control can be gained by installing a differential en- thalpy sensor in the return air duct. When differential enthalpy control is installed, the economizer control will use the air stream with lower enthalpy (outside air or return air) to pro- vide for lower compressor operating costs during integrated economizer cycle operation. The differential enthalpy sen- sor is installed in the
10