Table 29 Ð Carrier Default Program Parameter Values
PARAMETER GROUP | PARAMETER | DEFAULT VALUE | |
| ACC1 | 60.0 Sec | |
| DEC1 | 60.0 Sec | |
| UL | 60.0 Hz | |
| LL | 10.0 Hz* | |
| Luln | 1 | |
| P3 | 20% | |
SEtP | 0.0 Hz | ||
(Setup) | P4 | 100% | |
| 60 Hz | ||
| tHr1 | See Table 31 | |
| StC1 | 0 | |
| StL1 | 110% | |
| OLN | 1 | |
| tYP | 5* | |
Gr.F | FH | 60 Hz | |
(Fundamental) | Pt | 2 | |
| FbP1 | 1* | |
| Fbln | 2 | |
| GP | .30 | |
| Gl | 2 sec | |
Gr.Fb | GA | 0 | |
(Feedback) | GFS | 80 | |
| P1LL | 10 | |
| PuL | 1 | |
| PuUl | 10 | |
| PuLL | 10 | |
Gr.SF | Fsor | 60 Hz | |
Sr.n | 1* | ||
(Frequency Settings) | |||
SrN1 | 0* | ||
| |||
Gr.Pn | Fr | 0* | |
(Panel Control) | |||
|
| ||
| 1t | 1 | |
| 1t0 | 0 | |
Gr.St | 1t1 | 56 | |
(Terminal Selection) | 1t2 | 13 | |
| 1t3 | 3 | |
| 1t4 | 10 | |
Gr.Pr | UuC | 1* | |
UuCt | 2 | ||
(Protection) | |||
ArSt | 3 | ||
| |||
| Cnod | 1* | |
Gr.Ut | bLSF | 1* | |
(Utility) | Fnod | 2* | |
| bLPn | 1* |
*These settings differ from the Toshiba defaults and are required for Carrier applications.
NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SetP). This restores the VFD original factory settings.
53