Carrier 48FK Potentiometer Inputs and Ranges, Conguration Header DIP Switch Factory Settings

Page 26

Table 9 Ð Potentiometer Inputs and Ranges

 

 

 

CONTROL

 

POTENTIOMETER

DESCRIPTION

LOCATION

VALID

DEFAULT VALUE

 

 

 

RANGE

 

P1

Supply Air

Display

45 to 70 F

45 F if -22 F < P1 < 45 F

Set Point

Board

70 F if P1 > 70 F OR IF P1 < -22 F

 

 

P2*

Economizer

Economizer

0 to 100%

None (0 if P2 is bad)

Position

Motor

 

 

 

P3

Reset Limit

Accessory

0 to 80 F

None (limited to 70 F maximum)

Board

 

 

 

 

P4²

Demand Limit,

Main Control Box

0 to 100%

None

Single-Step

 

 

 

 

DLCM-P1

Demand Limit,

DLCM Board

50 to 100%

None

DLCM-P2

2-Step

DLCM Board

0 to 49%

None

P5*

Minimum Economizer

Accessory Board

0 to 100%

None

Position

 

 

 

 

P6

Warm-Up

 

 

40 F if 0° F < P6 < 40 F OR IF P6 < 95 F

Accessory Board

40 to 80 F

OR IF P6 < 0

Set Point

 

 

 

80 F if 80 F < P6 < 95 F

 

 

 

 

P7**

Reset

Reset Board

40 to 100 F

None

Temperature

 

 

 

 

*Optional factory-installed economizer is required. Potentiometer P2 is not a set point.

²Accessory two-step demand limit module is required (which has 2 potentiometers), o r a 5 to 20 k-ohm ®eld-supplied potentiometer is required for single-step demand limit.

**Accessory temperature reset is required.

NOTE: Potentiometers P1-P6 input data to pin terminal connector J3.

Potentiometer P7 inputs data to pin terminal connector J1.

Con®guration Header Ð The con®guration header is a series of 8 small wires that are broken (open circuit) or unbroken (closed circuit) in a pattern to indicate several unique characteristics of the unit. The con®guration header is fac- tory set and should not be changed; changing the factory set- ting may cause the unit to malfunction.

Before start-up, visually check the con®guration header against the factory setting for the unit size. See Table 10 for factory settings. See Table 11 for purpose for each jumper.

Table 10 Ð Con®guration Header and

DIP Switch Factory Settings

 

UNIT SIZES

UNIT SIZE

UNIT SIZE

 

034-038,

JUMPER OR

044

104

048-088

SWITCH NO.

 

 

 

 

 

 

Header

Switch

Header

Switch

Header

Switch

 

 

Position

Position

Position

Position

Position

Position

1

 

Off

 

Off

 

Off

2

 

Off

 

Off

 

Off

3

 

On/Off*

 

On/Off*

 

On/Off*

4

 

On/Off*

 

On/Off*

 

On/Off*

5

 

Off

 

Off

 

Off

6

 

Off

 

On

 

On

7

 

On

 

Off

 

Off

8

 

Off

 

Off

 

Off

 

 

 

 

 

 

 

LEGEND

DIP Ð Dual, In-Line Package

ÐBroken Jumper (open circuit)

ÐUnbroken Jumper (closed circuit)

*Depending on factory-installed options or ®eld-installed accessories.

Table 11 Ð Con®guration Header Jumpers

JUMPER

FUNCTION

FACTORY

MEANING

NUMBER

SETTING

 

 

1,2

Unit Type

 

VAV Rooftop Unit

3,4,5

Qty Compressors

 

2 Compressors

6

Expansion Valve

 

TXV

7

Power Frequency

 

60 Hz

8

Not Used

 

No Signi®cance

 

 

 

 

LEGEND

TXV Ð Thermostatic Expansion Valve

VAV Ð Variable-Air Volume

ÐBroken Jumper (open circuit)

ÐUnbroken Jumper (closed circuit)

DIP Switches Ð The DIP switches con®gure the unit for several factory-installed options and ®eld-installed ac- cessories, plus factory unloaders. The DIP switches are lo- cated under a plastic enclosure which must be removed for access. See Fig. 1. The switches can be ®eld adjusted. Switches must only be adjusted when control power is deenergized. See Table 12 for DIP switch purposes and Table 10 for fac- tory settings of the switch positions.

Disconnect control power before changing the settings of the DIP switches. To disconnect control power, open the control circuit breaker.

26

Image 26
Contents Controls Operation Troubleshooting ContentsSafety Considerations GeneralDIP Pin Terminal Connector J1 Thermistor InputsConnector J1 Temperature Unit Size Terminal no Input EXV034-104 Status Switch InputsConnector J2 Status Switch Unit Size Terminal no RNT Ð ReturnPage HIR Output Pin and Terminal AssignmentsOutput PIN Name Rating Device Terminal IFCCompressor Operation Thermistor T1 Location, 50FK,JK034-048 Units Thermistor T1 Location, 50FK,JK054-074 Units Thermistor T2 Location, Size 034-048 Units Thermistor T3 and T4 Locations, Size 054-104 Units Integrated Circuit InputControls Installation Space Temperature ResetUnit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes Unit Control Box Arrangement, Sizes 088 Voltage Drop Characteristics Thermistor ResistanceSpace Temperature Sensor Averaging Single-Step Demand Limit MSP = Sasp + Remote Sasp Wiring Smoke Control Switches Required for Each Mode Smoke Control ModesSwitch Functions Tubing SizeTerminal Block DPS Ð Differential Pressure SwitchSwitch Modulating Power Exhaust Differential Pressure Switch Sizes START-UPConguration Header Jumpers Conguration Header DIP Switch Factory SettingsPotentiometer Inputs and Ranges DIP Switches Switch Function Meaning PositionInlet Guide Vane Motor 50FK,JK034-074 Units Jumper Removal to Disable Motor Variable Frequency Drive KeypadControl Signal Pressure VFD SET Point VFD Set Point Frequency Command for Duct PressureChanging the VFD Set Point Frequency Command PressureStart Unit Quick Test, Unit Conguration and Switch Check Quick Normal Description Control Switch Test Display Step noQuick Normal Description Thermistor or Test Quick Test, Thermistor and Potentiometer CheckQuick Test, Output Relay Check Quick Normal Test Description Relay NumberOperating Information Sensor Resistance ValuesPage Component Arrangement, 034-048 Units Component Arrangement, 054-104 Units Page Modulating Power Exhaust Component Locations Sizes Modulating Power Exhaust Component Locations Sizes Page Compressor Loading and Unloading Sequences Cooling Size 088 Units Cooling Size 054 UnitsCooling Size 064 Units Cooling Size 104 UnitsSymptoms Probable Causes Solutions TroubleshootingControls Troubleshooting Operation Status CodesDiagnostic Codes Codes 71 to 76 THERMISTOR/RESISTOR Failure Page TP4 Terminals Voltage ACTest PIN Voltage DC TP3 TP6Quick Test J9 PIN Numbers Step no PIN Terminal Voltage DCTerminal Strip J6 Connection Resistance Reading Pin Terminal Connector J1 VoltagesPin Terminal Connector J2 Voltages PIN Voltage TerminalQuick Test J5 PIN Numbers Step no Terminal Strip J5 Connector Resistance ReadingEnthalpy Sensor Checkout Variable Frequency Drive Carrier Default Program Parameter Values Parameter Group Default ValueRequired User Adjusted Defaults Motor Overload SettingsLPS ALMLAT MTRPage Page Service Training Call for Free CatalogII. Preliminary Checklist Items PRE-START-UPIII. START-UP IV. Notes